Costo de construcción de redes aereas

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (rural) Poste de Madera
Descripción Materiales y equipo de instalación permanente
($)
Mano de obra
($)
Diseño del proyecto
($)
Supervision
($)
Costo total /Km
($)
Retiro
($)
1C-1F-2H-13 kV-1/0-AWG-ACSR-PM (RURAL) 72,453.32 34,459.92 1,586.74 1,506.41 110,006.39 17,657.24
1C-1F-2H-13 kV-3/0-AWG-ACSR-PM (RURAL) 78,201.35 60,132.04 1,586.74 1,506.41 141,426.53 17,657.24
1C-1F-2H-13 kV-266.8-AWG-ACSR-PM (RURAL) 96,236.09 60,132.04 1,586.74 1,506.41 159,461.27 17,657.24
1C-1F-2H-23 kV-1/0-AWG-ACSR-PM (RURAL) 73,297.97 34,459.92 1,586.74 1,506.41 110,851.03 17,657.24
1C-1F-2H-23 kV-3/0-AWG-ACSR-PM (RURAL) 79,045.98 60,132.04 1,586.74 1,506.41 142,271.17 17,657.24
1C-1F-2H-23 kV-266.8-AWG-ACSR-PM (RURAL) 97,080.73 60,132.04 1,586.74 1,506.41 160,305.92 17,657.24
1C-1F-2H-33 kV-1/0-AWG-ACSR-PM (RURAL) 77,036.52 34,459.92 1,586.74 1,506.41 114,589.59 17,657.24
1C-1F-2H-33 kV-3/0-AWG-ACSR-PM (RURAL) 82,784.55 60,132.04 1,586.74 1,506.41 146,009.73 17,657.24
1C-1F-2H-33 kV-266.8-AWG-ACSR-PM (RURAL) 100,819.29 60,132.04 1,586.74 1,506.41 164,044.47 17,657.24
1C-2F-3H-13 kV-1/0-2-AWG-CU-PM (RURAL) 319,600.27 39,706.28 1,586.74 1,759.18 362,652.48 17,657.24
1C-2F-3H-13 kV-1/0-AWG-ACSR-PM (RURAL) 96,768.04 38,759.18 1,586.74 1,759.18 138,873.15 17,657.24
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PM (RURAL) 466,481.09 40,153.17 1,586.74 1,759.18 509,980.19 17,657.24
1C-2F-3H-13 kV-3/0-AWG-ACSR-PM (RURAL) 108,264.09 90,103.40 1,586.74 1,759.18 201,713.41 17,657.24
1C-2F-3H-13 kV-2-AWG-CU-PM (RURAL) 247,243.50 38,759.18 1,586.74 1,759.18 289,348.61 17,657.24
1C-2F-3H-13 kV-266.8-AWG-ACSR-PM (RURAL) 146,038.81 90,156.73 1,586.74 1,759.18 239,541.47 17,657.24
1C-2F-3H-23 kV-1/0-AWG-ACSR-PM (RURAL) 98,370.31 38,759.18 1,941.13 1,759.18 140,829.80 17,657.24
1C-2F-3H-23 kV-3/0-AWG-ACSR-PM (RURAL) 109,866.36 90,103.40 1,941.13 1,759.18 203,670.07 17,657.24
1C-2F-3H-23 kV-266.8-AWG-ACSR-PM (RURAL) 147,641.08 90,156.73 1,586.74 1,759.18 241,143.73 17,657.24
1C-2F-3H-33 kV-1/0-AWG-ACSR-PM (RURAL) 106,876.09 38,759.18 1,586.74 1,759.18 148,981.20 17,657.24
1C-2F-3H-33 kV-3/0-AWG-ACSR-PM (RURAL) 118,372.14 90,103.40 1,586.74 1,759.18 211,821.46 17,657.24
1C-2F-3H-33 kV-266.8-AWG-ACSR-PM (RURAL) 156,146.86 90,156.73 1,586.74 1,759.18 249,649.51 17,657.24
1C-3F-4H-13 kV-1/0-2-AWG-CU-PM (RURAL) 420,793.55 44,642.32 1,586.74 2,011.96 469,034.58 17,657.24
1C-3F-4H-13 kV-1/0-AWG-ACSR-PM (RURAL) 112,463.38 43,301.66 1,586.74 2,011.96 159,363.74 17,657.24
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PM (RURAL) 623,451.90 45,089.21 1,586.74 2,011.96 672,139.82 17,657.24
1C-3F-4H-13 kV-3/0-AWG-ACSR-PM (RURAL) 129,707.45 120,318.00 1,586.74 2,011.96 253,624.16 17,657.24
1C-3F-4H-13 kV-2-AWG-CU-PM (RURAL) 313,097.33 43,301.66 1,586.74 2,011.96 359,997.69 17,657.24
1C-3F-4H-13 kV-266.8-AWG-ACSR-PM (RURAL) 185,530.61 120,318.00 1,586.74 2,011.96 309,447.32 17,657.24
1C-3F-4H-13 kV-336.4-AWG-ACSR-PM (RURAL) 209,435.08 121,658.67 1,586.74 2,011.96 334,692.46 17,657.24
1C-3F-4H-13 kV-477-AWG-ACSR-PM (RURAL) 266,798.26 121,765.65 1,524.74 1,999.42 392,088.07 17,657.24
1C-3F-4H-23 kV-1/0-AWG-ACSR-PM (RURAL) 114,794.61 43,301.66 1,586.74 2,011.96 161,694.97 17,657.24
1C-3F-4H-23 kV-3/0-AWG-ACSR-PM (RURAL) 132,038.68 120,318.00 1,586.74 2,011.96 255,955.39 17,657.24
1C-3F-4H-23 kV-266.8-AWG-ACSR-PM (RURAL) 187,934.01 120,318.00 1,586.74 2,011.96 311,850.72 17,657.24
1C-3F-4H-23 kV-336.4-AWG-ACSR-PM (RURAL) 211,838.48 121,658.67 1,586.74 2,011.96 337,095.85 17,657.24
1C-3F-4H-23 kV-477-AWG-ACSR-PM (RURAL) 268,797.93 121,765.65 1,524.74 1,999.42 394,087.74 17,657.24
1C-3F-4H-33 kV-1/0-AWG-ACSR-PM (RURAL) 129,143.77 37,388.02 1,586.74 2,011.96 170,130.50 18,850.86
1C-3F-4H-33 kV-3/0-AWG-ACSR-PM (RURAL) 144,519.87 120,318.00 1,586.74 2,011.96 268,436.58 18,850.86
1C-3F-4H-33 kV-266.8-AWG-ACSR-PM (RURAL) 200,492.08 120,318.00 1,586.74 2,011.96 324,408.79 18,850.86
1C-3F-4H-33 kV-336.4-AWG-ACSR-PM (RURAL) 224,396.55 121,658.67 1,586.74 2,011.96 349,653.92 18,850.86
1C-3F-4H-33 kV-477-AWG-ACSR-PM (RURAL) 280,416.02 121,765.65 1,524.74 1,999.42 405,705.83 17,657.24

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,465.93
Costo por conexión de línea de 2 fases : $ 1,873.12
Costo por conexión de línea de 3 fases : $ 2,122.76

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (rural) Poste de Concreto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PC (RURAL) 78,419.21 35,313.98 1,524.74 1,493.86 116,751.79 17,657.24
1C-1F-2H-13 kV-3/0-AWG-ACSR-PC (RURAL) 84,167.22 60,986.09 1,524.74 1,493.86 148,171.92 17,657.24
1C-1F-2H-13 kV-266.8-AWG-ACSR-PC (RURAL) 102,201.97 60,986.09 1,524.74 1,493.86 166,206.67 17,657.24
1C-1F-2H-23 kV-1/0-AWG-ACSR-PC (RURAL) 81,189.05 35,313.98 1,524.74 1,493.86 119,521.63 17,657.24
1C-1F-2H-23 kV-3/0-AWG-ACSR-PC (RURAL) 86,937.08 60,986.09 1,524.74 1,493.86 150,941.77 17,657.24
1C-1F-2H-23 kV-266.8-AWG-ACSR-PC (RURAL) 104,971.81 60,986.09 1,524.74 1,493.86 168,976.51 17,657.24
1C-1F-2H-33 kV-1/0-AWG-ACSR-PC (RURAL) 81,760.40 35,313.98 1,524.74 1,493.86 120,092.98 17,657.24
1C-1F-2H-33 kV-3/0-AWG-ACSR-PC (RURAL) 87,508.42 60,986.09 1,524.74 1,493.86 151,513.12 17,657.24
1C-1F-2H-33 kV-266.8-AWG-ACSR-PC (RURAL) 105,543.17 60,986.09 1,524.74 1,493.86 169,547.87 17,657.24
1C-2F-3H-13 kV-1/0-2-AWG-CU-PC (RURAL) 313,660.90 40,560.34 1,524.74 1,746.64 357,492.62 17,657.24
1C-2F-3H-13 kV-1/0-AWG-ACSR-PC (RURAL) 92,533.90 39,666.57 1,524.74 1,746.64 135,471.85 17,657.24
1C-2F-2H 13 KV 1/0 AWG AAC-PC RURAL 70,713.29 33,679.85 1,524.74 1,493.86 107,411.74 17,657.24
1C-2F-2H 13 KV 1/0 AWG ACSR-PC RURAL 75,956.79 33,679.85 1,524.74 1,493.86 112,655.24 17,657.24
1C-2F-2H 13 KV 1/0 AWG Cu-PC RURAL 246,925.29 34,573.63 1,524.74 1,493.86 284,517.52 17,657.24
1C-2F-2H 13 KV 3/0 AWG AAC-PC RURAL 78,958.00 33,679.85 1,524.74 1,493.86 115,656.45 17,657.24
1C-2F-2H 13 KV 3/0 AWG ACSR-PC RURAL 87,452.83 85,024.08 1,524.74 1,493.86 175,495.50 17,657.24
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PC (RURAL) 460,541.72 41,007.23 1,524.74 1,746.64 504,820.33 17,657.24
1C-2F-3H-13 kV-3/0-AWG-ACSR-PC (RURAL) 104,029.95 91,010.79 1,524.74 1,746.64 198,312.12 17,657.24
1C-2F-3H-13 kV-2-AWG-CU-PC (RURAL) 243,009.37 39,666.57 1,524.74 1,746.64 285,947.32 17,657.24
1C-2F-3H-13 kV-266.8-AWG-ACSR-PC (RURAL) 140,099.44 91,010.79 1,524.74 1,746.64 234,381.61 17,657.24
1C-2F-2H 13 KV 2 AWG Cu-PC RURAL 176,273.75 33,679.85 1,524.74 1,493.86 212,972.20 17,657.24
1C-2F-3H-23 kV-1/0-AWG-ACSR-PC (RURAL) 98,103.33 39,666.57 1,524.74 1,746.64 141,041.28 17,657.24
1C-2F-3H-23 kV-3/0-AWG-ACSR-PC (RURAL) 109,599.36 91,010.79 1,524.74 1,746.64 203,881.53 17,657.24
1C-2F-3H-23 kV-266.8-AWG-ACSR-PC (RURAL) 145,668.86 91,010.79 1,524.74 1,746.64 239,951.03 17,657.24
1C-2F-3H-33 kV-1/0-AWG-ACSR-PC (RURAL) 96,565.89 39,666.57 1,524.74 1,746.64 139,503.84 17,657.24
1C-2F-3H-33 kV-3/0-AWG-ACSR-PC (RURAL) 108,061.94 91,010.79 1,524.74 1,746.64 202,344.10 17,657.24
1C-2F-3H-33 kV-266.8-AWG-ACSR-PC (RURAL) 144,131.43 91,010.79 1,524.74 1,746.64 238,413.59 17,657.24
1C-3F-3H-13 KV-1/0-AWG-ACSR-PC (RURAL) 92,284.62 38,032.44 1,524.74 1,746.64 133,588.43 17,657.24
1C-3F-3H 13 KV 1/0 AWG AAC-PC RURAL 84,419.37 38,032.44 1,524.74 1,746.64 125,723.18 17,657.24
1C-3F-3H 13 KV 1/0 AWG SA-AAC-PC RURAL 166,621.82 46,370.31 1,524.74 1,746.64 216,263.52 17,657.24
1C-3F-4H-13 kV-1/0-2-AWG-CU-PC (RURAL) 413,784.67 45,496.39 1,524.74 1,999.42 462,805.22 17,657.24
1C-3F-4H-13 kV-1/0-AWG-ACSR-PC (RURAL) 107,173.43 44,155.73 1,524.74 1,999.42 154,853.32 17,657.24
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PC (RURAL) 616,443.02 45,943.27 1,524.74 1,999.42 665,910.45 17,657.24
1C-3F-4H-13 kV-3/0-AWG-ACSR-PC (RURAL) 124,417.50 121,172.06 1,524.74 1,999.42 249,113.72 17,657.24
1C-3F-3H-13 KV-3/0-AWG-ACSR-PC (RURAL) 109,528.67 115,048.77 1,524.74 1,746.64 227,848.82 17,657.24
1C-3F-3H 13 KV 3/0 AWG AAC-PC RURAL 96,786.43 38,032.44 1,524.74 1,746.64 138,090.25 17,657.24
1C-3F-3H 13 KV 3/0 AWG SA-AAC-PC RURAL 183,020.41 46,370.31 1,524.74 1,746.64 232,662.10 17,657.24
1C-3F-3H-13 KV-266.8-AWG-ACSR-PC (RURAL) 163,632.91 115,048.77 1,524.74 1,746.64 281,953.06 17,657.24
1C-3F-3H 13 KV 266 AWG AAC-PC RURAL 120,182.14 38,032.44 1,524.74 1,746.64 161,485.96 17,657.24
1C-3F-3H 13 KV 266 AWG SA-AAC-PC RURAL 238,759.47 46,370.31 1,524.74 1,746.64 288,401.16 17,657.24
1C-3F-4H-13 kV-2-AWG-CU-PC (RURAL) 307,807.37 44,155.73 1,524.74 1,999.42 355,487.26 17,657.24
1C-3F-4H-13 kV-266.8-AWG-ACSR-PC (RURAL) 178,521.74 121,172.06 1,524.74 1,999.42 303,217.96 17,657.24
1C-3F-4H-13 kV-336.4-AWG-ACSR-PC (RURAL) 202,426.21 122,512.72 1,524.74 1,999.42 328,463.09 17,657.24
1C-3F-3H-13 KV-336.4-AWG-ACSR-PC (RURAL) 187,537.40 116,389.43 1,524.74 1,746.64 307,198.21 17,657.24
1C-3F-3H 13 KV 336 AWG AAC-PC RURAL 138,971.74 39,373.10 1,524.74 1,746.64 181,616.22 17,657.24
1C-3F-3H 13 KV 336 AWG SA-AAC-PC RURAL 289,368.92 46,370.31 1,524.74 1,746.64 339,010.62 17,657.24
1C-3F-3H 13 KV 477 AWG AAC-PC RURAL 170,268.78 39,373.10 1,524.74 1,746.64 212,913.26 17,657.24
1C-3F-3H-13 KV-477-AWG-ACSR-PC (RURAL) 241,006.01 116,389.43 1,524.74 1,746.64 360,666.82 17,657.24
1C-3F-4H-13 kV-477-AWG-ACSR-PC (RURAL) 255,894.82 122,512.72 1,524.74 1,999.42 381,931.70 17,657.24
1C-3F-4H-23 kV-1/0-AWG-ACSR-PC (RURAL) 116,521.64 44,155.73 1,524.74 1,999.42 164,201.52 17,657.24
1C-3F-3H-23 KV-1/0-AWG-ACSR-PC (RURAL) 99,535.56 38,032.44 1,524.74 1,746.64 140,839.38 17,657.24
1C-3F-3H 23 KV 1/0 AWG AAC-PC RURAL 91,670.31 38,032.44 1,524.74 1,746.64 132,974.13 17,657.24
1C-3F-3H 23 KV 1/0 AWG SA-AAC-PC RURAL 207,235.43 46,370.31 1,524.74 1,746.64 256,877.12 17,657.24
1C-3F-3H 23 KV 3/0 AWG AAC-PC RURAL 104,037.38 38,032.44 1,524.74 1,746.64 145,341.20 17,657.24
1C-3F-3H 23 KV 3/0 AWG SA-AAC-PC RURAL 212,082.30 46,370.31 1,524.74 1,746.64 261,724.00 17,657.24
1C-3F-3H-23 KV-3/0-AWG-ACSR-PC (RURAL) 116,779.63 115,048.77 1,524.74 1,746.64 235,099.78 17,657.24
1C-3F-4H-23 kV-3/0-AWG-ACSR-PC (RURAL) 133,765.70 121,172.06 1,524.74 1,999.42 258,461.92 17,657.24
1C-3F-4H-23 kV-266.8-AWG-ACSR-PC (RURAL) 187,869.94 121,172.06 1,524.74 1,999.42 312,566.17 17,657.24
1C-3F-3H-23 KV-266.8-AWG-ACSR-PC (RURAL) 170,883.87 115,048.77 1,524.74 1,746.64 289,204.02 17,657.24
1C-3F-3H 23 KV 266 AWG AAC-PC RURAL 127,433.10 38,032.44 1,524.74 1,746.64 168,736.91 17,657.24
1C-3F-3H 23 KV 266 AWG SA-AAC-PC RURAL 249,241.68 46,370.31 1,524.74 1,746.64 298,883.37 17,657.24
1C-3F-3H 23 KV 336 AWG AAC-PC RURAL 146,222.70 39,373.10 1,524.74 1,746.64 188,867.18 17,657.24
1C-3F-3H 23 KV 336 AWG SA-AAC-PC RURAL 296,619.87 46,370.31 1,524.74 1,746.64 346,261.56 17,657.24
1C-3F-3H-23 KV-336.4-AWG-ACSR-PC (RURAL) 194,788.34 116,389.43 1,524.74 1,746.64 314,449.15 17,657.24
1C-3F-4H-23 kV-336.4-AWG-ACSR-PC (RURAL) 211,774.43 122,512.72 1,524.74 1,999.42 337,811.31 17,657.24
1C-3F-4H-23 kV-477-AWG-ACSR-PC (RURAL) 265,243.03 122,512.72 1,524.74 1,999.42 391,279.91 17,657.24
1C-3F-3H-23 KV-477-AWG-ACSR-PC (RURAL) 248,256.95 116,389.43 1,524.74 1,746.64 367,917.76 17,657.24
1C-3F-3H 23 KV 477 AWG AAC-PC RURAL 177,519.72 39,373.10 1,524.74 1,746.64 220,164.20 17,657.24
1C-3F-3H 33 KV 1/0 AWG AAC-PC RURAL 91,735.55 38,032.44 1,524.74 1,746.64 133,039.37 17,657.24
1C-3F-3H 33 KV 1/0 AWG SA-AAC-PC RURAL 246,075.67 46,370.31 1,524.74 1,746.64 295,717.36 17,657.24
1C-3F-3H-33 KV-1/0-AWG-ACSR-PC (RURAL) 99,600.80 38,032.44 1,524.74 1,746.64 140,904.62 17,657.24
1C-3F-4H-33 kV-1/0-AWG-ACSR-PC (RURAL) 113,842.33 44,155.73 1,524.74 1,999.42 161,522.22 17,657.24
1C-3F-3H-33 KV-3/0-AWG-ACSR-PC (RURAL) 116,844.87 115,048.77 1,524.74 1,746.64 235,165.02 17,657.24
1C-3F-3H 33 KV 3/0 AWG AAC-PC RURAL 104,102.63 38,032.44 1,524.74 1,746.64 145,406.45 17,657.24
1C-3F-3H 33 KV 3/0 AWG SA-AAC-PC RURAL 240,542.15 46,370.31 1,524.74 1,746.64 290,183.84 17,657.24
1C-3F-4H-33 kV-3/0-AWG-ACSR-PC (RURAL) 131,086.40 121,172.06 1,524.74 1,999.42 255,782.62 17,657.24
1C-3F-3H-33 KV-226.8-AWG-ACSR-PC (RURAL) 170,949.11 115,048.77 1,524.74 1,746.64 289,269.26 17,657.24
1C-3F-3H 33 KV 266 AWG AAC-PC RURAL 127,498.33 38,032.44 1,524.74 1,746.64 168,802.15 17,657.24
1C-3F-3H 33 KV 266 AWG SA-AAC-PC RURAL 253,871.06 46,370.31 1,524.74 1,746.64 303,512.75 17,657.24
1C-3F-4H-33 kV-266.8-AWG-ACSR-PC (RURAL) 185,190.64 121,172.06 1,524.74 1,999.42 309,886.86 17,657.24
1C-3F-3H-33 KV-336.4-AWG-ACSR-PC (RURAL) 194,853.58 116,389.43 1,524.74 1,746.64 314,514.39 17,657.24
1C-3F-3H 33 KV 336 AWG AAC-PC RURAL 146,287.94 39,373.10 1,524.74 1,746.64 188,932.42 17,657.24
1C-3F-3H 33 KV 336 AWG SA-AAC-PC RURAL 303,228.39 46,370.31 1,524.74 1,746.64 352,870.09 17,657.24
1C-3F-4H-33 kV-336.4-AWG-ACSR-PC (RURAL) 209,095.11 122,512.72 1,524.74 1,999.42 335,131.99 17,657.24
1C-3F-4H-33 kV-477-AWG-ACSR-PC (RURAL) 262,563.72 122,512.72 1,524.74 1,999.42 388,600.60 17,657.24
1C-3F-3H 33 KV 477 AWG AAC-PC RURAL 177,584.97 39,373.10 1,524.74 1,746.64 220,229.45 17,657.24
1C-3F-3H-33 KV-477-AWG-ACSR-PC (RURAL) 248,322.19 116,389.43 1,524.74 1,746.64 367,983.00 17,657.24

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,465.93
Costo por conexión de línea de 2 fases : $ 1,873.12
Costo por conexión de línea de 3 fases : $ 2,122.76

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (urbana) Poste de Madera
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PM (URBANA) 119,871.71 55,623.32 2,819.22 2,347.70 180,661.95 33,709.30
1C-1F-2H-13 kV-3/0-AWG-AAC-PM (URBANA) 121,372.32 55,623.32 2,819.22 2,347.70 182,162.56 33,709.30
1C-1F-2H-13 kV-266.8-AWG-AAC-PM (URBANA) 129,170.89 55,623.32 2,819.22 2,347.70 189,961.13 33,709.30
1C-1F-2H-23 kV-1/0-AWG-ACSR-PM (URBANA) 122,301.34 55,569.99 2,819.22 2,347.70 183,038.26 33,709.30
1C-1F-2H-23 kV-3/0-AWG-AAC-PM (URBANA) 123,801.95 55,569.99 2,819.22 2,347.70 184,538.86 33,709.30
1C-1F-2H-23 kV-266.8-AWG-AAC-PM (URBANA) 131,600.52 55,569.99 2,819.22 2,347.70 192,337.43 33,709.30
1C-1F-2H-33 kV-1/0-AWG-ACSR-PM (URBANA) 129,921.27 55,569.99 2,819.22 2,347.70 190,658.18 33,709.30
1C-1F-2H-33 kV-3/0-AWG-AAC-PM (URBANA) 131,421.88 55,569.99 2,819.22 2,347.70 192,158.79 33,709.30
1C-1F-2H-33 kV-266.8-AWG-AAC-PM (URBANA) 139,220.45 55,569.99 2,819.22 2,347.70 199,957.36 33,709.30
1C-2F-3H-13 kV-1/0-2-AWG-CU-PM (URBANA) 382,478.61 62,541.88 2,819.22 2,600.48 450,440.19 33,709.30
1C-2F-3H-13 kV-1/0-AWG-ACSR-PM (URBANA) 159,646.38 61,648.11 2,819.22 2,600.48 226,714.19 33,709.30
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PM (URBANA) 529,359.43 62,988.77 2,819.22 2,600.48 597,767.91 33,709.30
1C-2F-3H-13 kV-3/0-AWG-AAC-PM (URBANA) 162,647.61 61,648.11 2,819.22 2,600.48 229,715.42 33,709.30
1C-2F-3H-13 kV-266.8-AWG-AAC-PM (URBANA) 179,949.97 61,648.11 2,819.22 2,600.48 247,017.78 33,709.30
1C-2F-3H-13 kV-250-1/0-AWG-CU-PM (URBANA) 810,478.17 62,988.77 2,819.22 2,600.48 878,886.64 33,709.30
1C-2F-3H-23 kV-1/0-AWG-ACSR-PM (URBANA) 164,270.27 61,648.11 2,819.22 2,600.48 231,338.09 33,709.30
1C-2F-3H-23 kV-3/0-AWG-AAC-PM (URBANA) 167,271.50 61,648.11 2,819.22 2,600.48 234,339.31 33,709.30
1C-2F-3H-23 kV-266.8-AWG-AAC-PM (URBANA) 184,573.86 61,648.11 2,819.22 2,600.48 251,641.67 33,709.30
1C-2F-3H-33 kV-1/0-AWG-ACSR-PM (URBANA) 181,595.44 61,648.11 2,819.22 2,600.48 248,663.25 33,709.30
1C-2F-3H-33 kV-3/0-AWG-AAC-PM (URBANA) 184,596.66 61,648.11 2,819.22 2,600.48 251,664.48 33,709.30
1C-2F-3H-33 kV-266.8-AWG-AAC-PM (URBANA) 201,899.03 61,648.11 2,819.22 2,600.48 268,966.84 33,709.30
1C-3F-4H-13 kV-1/0-2-AWG-CU-PM (URBANA) 485,296.80 68,183.93 2,819.22 2,853.25 559,153.20 33,709.30
1C-3F-4H-13 kV-1/0-AWG-ACSR-PM (URBANA) 176,966.63 66,843.27 2,819.22 2,853.25 249,482.36 33,709.30
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PM (URBANA) 687,955.15 68,630.82 2,819.22 2,853.25 762,258.44 33,709.30
1C-3F-4H-13 kV-3/0-AWG-AAC-PM (URBANA) 181,468.46 66,843.27 2,819.22 2,853.25 253,984.19 33,709.30
1C-3F-4H-13 kV-266.8-AWG-AAC-PM (URBANA) 206,583.09 66,843.27 2,819.22 2,853.25 279,098.82 33,709.30
1C-3F-4H-13 kV-336.4-AWG-AAC-PM (URBANA) 225,372.69 68,183.93 2,819.22 2,853.25 299,229.09 33,709.30
1C-3F-4H-13 kV-477-AWG-AAC-PM (URBANA) 262,706.68 68,183.93 2,819.22 2,853.25 336,563.08 33,709.30
1C-3F-4H-13 kV-250-1/0-AWG-CU-PM (URBANA) 1,109,633.25 68,630.82 2,819.22 2,853.25 1,183,936.55 33,709.30
1C-3F-4H-23 kV-1/0-AWG-ACSR-PM (URBANA) 183,426.57 66,843.27 2,819.22 2,853.25 255,942.31 33,709.30
1C-3F-4H-23 kV-3/0-AWG-AAC-PM (URBANA) 187,928.40 66,843.27 2,819.22 2,853.25 260,444.14 33,709.30
1C-3F-4H-23 kV-266.8-AWG-AAC-PM (URBANA) 213,115.20 66,843.27 2,819.22 2,853.25 285,630.94 33,709.30
1C-3F-4H-23 kV-336.4-AWG-AAC-PM (URBANA) 231,904.80 68,183.93 2,819.22 2,853.25 305,761.20 33,709.30
1C-3F-4H-23 kV-477-AWG-AAC-PM (URBANA) 268,835.07 68,183.93 2,819.22 2,853.25 342,691.47 33,709.30
1C-3F-4H-33 kV-1/0-AWG-ACSR-PM (URBANA) 209,730.85 66,843.27 2,819.22 2,853.25 282,246.58 33,709.30
1C-3F-4H-33 kV-3/0-AWG-AAC-PM (URBANA) 214,232.68 66,843.27 2,819.22 2,853.25 286,748.41 33,709.30
1C-3F-4H-33 kV-266.8-AWG-AAC-PM (URBANA) 239,496.35 66,843.27 2,819.22 2,853.25 312,012.09 33,709.30
1C-3F-4H-33 kV-336.4-AWG-AAC-PM (URBANA) 258,285.95 68,183.93 2,819.22 2,853.25 332,142.35 33,709.30
1C-3F-4H-33 kV-477-AWG-AAC-PM (URBANA) 292,499.68 68,183.93 2,819.22 2,853.25 366,356.08 33,709.30

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 961.33
Costo por conexión de línea de 2 fases : $ 1,272.79
Costo por conexión de línea de 3 fases : $ 1,618.17

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (urbana) Poste de Concreto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PC (URBANA) 129,265.95 57,204.12 2,819.22 2,347.70 191,636.99 33,709.30
1C-1F-2H-13 kV-3/0-AWG-AAC-PC (URBANA) 130,766.56 57,204.12 2,819.22 2,347.70 193,137.60 33,709.30
1C-1F-2H-13 kV-266.8-AWG-AAC-PC (URBANA) 138,565.13 57,204.12 2,819.22 2,347.70 200,936.17 33,709.30
1C-1F-2H-23 kV-1/0-AWG-ACSR-PC (URBANA) 134,641.62 57,204.12 2,819.22 2,347.70 197,012.66 33,709.30
1C-1F-2H-23 kV-3/0-AWG-AAC-PC (URBANA) 136,142.22 57,204.12 2,819.22 2,347.70 198,513.27 33,709.30
1C-1F-2H-23 kV-266.8-AWG-AAC-PC (URBANA) 143,940.80 57,204.12 2,819.22 2,347.70 206,311.84 33,709.30
1C-1F-2H-33 kV-1/0-AWG-ACSR-PC (URBANA) 135,483.52 57,204.12 2,819.22 2,347.70 197,854.57 33,709.30
1C-1F-2H-33 kV-3/0-AWG-AAC-PC (URBANA) 136,984.13 57,204.12 2,819.22 2,347.70 199,355.17 33,709.30
1C-1F-2H-33 kV-266.8-AWG-AAC-PC (URBANA) 144,782.70 57,204.12 2,819.22 2,347.70 207,153.75 33,709.30
1C-2F-2H 13 KV 1/0 AWG AAC-PC URBANA 132,590.79 57,304.66 2,819.22 2,347.70 195,062.36 33,709.30
1C-2F-2H 13 KV 1/0 AWG ACSR-PC URBANA 137,834.28 57,304.66 2,819.22 2,347.70 200,305.86 33,709.30
1C-2F-2H 13 KV 1/0 AWG Cu-PC URBANA 149,330.32 108,648.89 2,819.22 2,347.70 263,146.13 33,709.30
1C-2F-3H-13 kV-1/0-2-AWG-CU-PC (URBANA) 375,563.22 64,176.01 2,819.22 2,600.48 445,158.93 33,709.30
1C-2F-3H-13 kV-1/0-AWG-ACSR-PC (URBANA) 154,436.23 63,282.24 2,819.22 2,600.48 223,138.18 33,709.30
1C-2F-2H 13 KV 3/0 AWG AAC-PC URBANA 140,835.50 57,304.66 2,819.22 2,347.70 203,307.07 33,709.30
1C-2F-2H 13 KV 3/0 AWG ACSR-PC URBANA 149,330.32 108,648.89 2,819.22 2,347.70 263,146.13 33,709.30
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PC (URBANA) 522,444.04 64,622.91 2,819.22 2,600.48 592,486.65 33,709.30
1C-2F-3H-13 kV-3/0-AWG-AAC-PC (URBANA) 157,437.44 63,282.24 2,819.22 2,600.48 226,139.39 33,709.30
1C-2F-3H-13 kV-266.8-AWG-AAC-PC (URBANA) 173,034.58 63,282.24 2,819.22 2,600.48 241,736.52 33,709.30
1C-2F-3H-13 kV-250-1/0-AWG-CU-PC (URBANA) 803,562.77 64,622.91 2,819.22 2,600.48 873,605.38 33,709.30
1C-2F-2H 13 KV 2 AWG Cu-PC URBANA 238,151.26 57,304.66 2,819.22 2,347.70 300,622.84 33,709.30
1C-2F-3H-23 kV-1/0-AWG-ACSR-PC (URBANA) 166,551.13 63,282.24 2,819.22 2,600.48 235,253.08 33,709.30
1C-2F-3H-23 kV-3/0-AWG-AAC-PC (URBANA) 169,552.34 63,282.24 2,819.22 2,600.48 238,254.29 33,709.30
1C-2F-3H-23 kV-266.8-AWG-AAC-PC (URBANA) 185,149.49 63,282.24 2,819.22 2,600.48 253,851.44 33,709.30
1C-2F-3H-33 kV-1/0-AWG-ACSR-PC (URBANA) 164,258.57 63,282.24 2,819.22 2,600.48 232,960.51 33,709.30
1C-2F-3H-33 kV-3/0-AWG-AAC-PC (URBANA) 167,259.78 63,282.24 2,819.22 2,600.48 235,961.72 33,709.30
1C-2F-3H-33 kV-266.8-AWG-AAC-PC (URBANA) 182,856.91 63,282.24 2,819.22 2,600.48 251,558.86 33,709.30
1C-3F-3H 13 KV 1/0 AWG AAC-PC URBANA 151,370.22 61,939.88 2,819.22 2,600.48 218,729.81 33,709.30
1C-3F-3H 13 KV 1/0 AWG Cu-PC URBANA 415,688.22 63,280.55 2,819.22 2,600.48 484,388.47 33,709.30
1C-3F-3H-13 KV-1/0-AWG-ACSR-PC (URBANA) 159,235.46 61,939.88 2,819.22 2,600.48 226,595.04 33,709.30
1C-3F-4H-13 kV-1/0-2-AWG-CU-PC (URBANA) 484,434.68 69,818.07 2,819.22 2,853.25 559,925.22 33,709.30
1C-3F-4H-13 kV-1/0-AWG-ACSR-PC (URBANA) 177,823.43 68,477.40 2,819.22 2,853.25 251,973.30 33,709.30
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PC (URBANA) 687,093.03 70,264.96 2,819.22 2,853.25 763,030.46 33,709.30
1C-3F-4H-13 kV-3/0-AWG-AAC-PC (URBANA) 182,325.26 68,477.40 2,819.22 2,853.25 256,475.13 33,709.30
1C-3F-3H-13 KV-3/0-AWG-ACSR-PC (URBANA) 176,479.53 138,956.21 2,819.22 2,600.48 320,855.44 33,709.30
1C-3F-3H 13 KV 3/0 AWG AAC-PC URBANA 163,737.29 61,939.88 2,819.22 2,600.48 231,096.87 33,709.30
1C-3F-3H 13 KV 3/0 AWG Cu-PC URBANA 583,020.80 63,280.55 2,819.22 2,600.48 651,721.05 33,709.30
1C-3F-3H-13 KV-266.8-AWG-ACSR-PC (URBANA) 230,583.77 138,956.21 2,819.22 2,600.48 374,959.68 33,709.30
1C-3F-3H 13 KV 266 AWG AAC-PC URBANA 187,133.00 61,939.88 2,819.22 2,600.48 254,492.58 33,709.30
1C-3F-4H-13 kV-266.8-AWG-AAC-PC (URBANA) 205,720.97 68,477.40 2,819.22 2,853.25 279,870.84 33,709.30
1C-3F-4H-13 kV-336.4-AWG-AAC-PC (URBANA) 224,510.57 69,818.07 2,819.22 2,853.25 300,001.10 33,709.30
1C-3F-3H 13 KV 336 AWG AAC-PC URBANA 205,922.60 63,280.55 2,819.22 2,600.48 274,622.85 33,709.30
1C-3F-3H-13 KV-336.4-AWG-ACSR-PC (URBANA) 254,488.25 140,296.88 2,819.22 2,600.48 400,204.83 33,709.30
1C-3F-3H-13 KV-477-AWG-ACSR-PC (URBANA) 307,956.86 140,296.88 2,819.22 2,600.48 453,673.44 33,709.30
1C-3F-3H 13 KV 477 AWG AAC-PC URBANA 237,219.63 63,280.55 2,819.22 2,600.48 305,919.88 33,709.30
1C-3F-4H-13 kV-477-AWG-AAC-PC (URBANA) 255,807.60 69,818.07 2,819.22 2,853.25 331,298.14 33,709.30
1C-3F-3H 13 KV 250 AWG Cu-PC URBANA 1,004,698.91 63,280.55 2,819.22 2,600.48 1,073,399.16 33,709.30
1C-3F-4H-13 kV-250-1/0-AWG-CU-PC (URBANA) 1,108,771.14 70,264.96 2,819.22 2,853.25 1,184,708.56 33,709.30
1C-3F-3H-23 KV-1/0-AWG-ACSR-PC (URBANA) 177,122.95 61,939.88 2,819.22 2,600.48 244,482.53 33,709.30
1C-3F-3H 23 KV 1/0 AWG AAC-PC URBANA 169,257.70 61,939.88 2,819.22 2,600.48 236,617.28 33,709.30
1C-3F-3H 23 KV 1/0 AWG Cu-PC URBANA 433,575.71 63,280.55 2,819.22 2,600.48 502,275.95 33,709.30
1C-3F-4H-23 kV-1/0-AWG-ACSR-PC (URBANA) 195,710.92 68,477.40 2,819.22 2,853.25 269,860.79 33,709.30
1C-3F-4H-23 kV-3/0-AWG-AAC-PC (URBANA) 200,212.74 68,477.40 2,819.22 2,853.25 274,362.60 33,709.30
1C-3F-3H 23 KV 3/0 AWG AAC-PC URBANA 181,624.78 61,939.88 2,819.22 2,600.48 248,984.36 33,709.30
1C-3F-3H 23 KV 3/0 AWG Cu-PC URBANA 600,908.29 63,280.55 2,819.22 2,600.48 669,608.54 33,709.30
1C-3F-3H-23 KV-3/0-AWG-ACSR-PC (URBANA) 194,367.01 138,956.21 2,819.22 2,600.48 338,742.93 33,709.30
1C-3F-3H-23 KV-266.8-AWG-ACSR-PC (URBANA) 248,471.25 138,956.21 2,819.22 2,600.48 392,847.17 33,709.30
1C-3F-3H 23 KV 266 AWG AAC-PC URBANA 205,020.48 61,939.88 2,819.22 2,600.48 272,380.06 33,709.30
1C-3F-4H-23 kV-266.8-AWG-AAC-PC (URBANA) 223,608.45 68,477.40 2,819.22 2,853.25 297,758.32 33,709.30
1C-3F-3H 23 KV 336 AWG AAC-PC URBANA 223,810.08 63,280.55 2,819.22 2,600.48 292,510.33 33,709.30
1C-3F-3H-23 KV-336.4-AWG-ACSR-PC (URBANA) 272,375.73 140,296.88 2,819.22 2,600.48 418,092.30 33,709.30
1C-3F-4H-23 kV-336.4-AWG-AAC-PC (URBANA) 242,398.06 69,818.07 2,819.22 2,853.25 317,888.59 33,709.30
1C-3F-4H-23 kV-477-AWG-AAC-PC (URBANA) 273,695.08 69,818.07 2,819.22 2,853.25 349,185.61 33,709.30
1C-3F-3H-23 KV-477-AWG-ACSR-PC (URBANA) 325,844.33 140,296.88 2,819.22 2,600.48 471,560.91 33,709.30
1C-3F-3H 23 KV 477 AWG AAC-PC URBANA 255,107.11 63,280.55 2,819.22 2,600.48 323,807.35 33,709.30
1C-3F-3H 23 KV 250 AWG Cu-PC URBANA 1,022,586.39 63,280.55 2,819.22 2,600.48 1,091,286.64 33,709.30
1C-3F-3H 33 KV 1/0 AWG AAC-PC URBANA 168,280.08 61,939.88 2,819.22 2,600.48 235,639.67 33,709.30
1C-3F-3H 33 KV 1/0 AWG Cu-PC URBANA 432,598.08 63,280.55 2,819.22 2,600.48 501,298.33 33,709.30
1C-3F-3H-33 KV-1/0-AWG-ACSR-PC (URBANA) 176,145.33 61,939.88 2,819.22 2,600.48 243,504.91 33,709.30
1C-3F-4H-33 kV-1/0-AWG-ACSR-PC (URBANA) 193,144.04 68,477.40 2,713.09 2,853.25 267,187.79 33,709.30
1C-3F-3H-33 KV-3/0-AWG-ACSR-PC (URBANA) 193,389.40 138,956.21 2,819.22 2,600.48 337,765.31 33,709.30
1C-3F-3H 33 KV 3/0 AWG AAC-PC URBANA 180,647.15 61,939.88 2,819.22 2,600.48 248,006.73 33,709.30
1C-3F-3H 33 KV 3/0 AWG Cu-PC URBANA 599,930.66 63,280.55 2,819.22 2,600.48 668,630.91 33,709.30
1C-3F-4H-33 kV-3/0-AWG-AAC-PC (URBANA) 197,645.87 68,477.40 2,713.09 2,853.25 271,689.62 33,709.30
1C-3F-3H 33 KV 266 AWG AAC-PC URBANA 204,042.86 61,939.88 2,819.22 2,600.48 271,402.44 33,709.30
1C-3F-4H-33 kV-266.8-AWG-AAC-PC (URBANA) 221,041.58 68,477.40 2,713.09 2,853.25 295,085.32 33,709.30
1C-3F-3H-33 KV-226.8-AWG-ACSR-PC (URBANA) 247,493.63 138,956.21 2,819.22 2,600.48 391,869.54 33,709.30
1C-3F-3H-33 KV-336.4-AWG-ACSR-PC (URBANA) 271,398.11 140,296.88 2,819.22 2,600.48 417,114.69 33,709.30
1C-3F-3H 33 KV 336 AWG AAC-PC URBANA 222,832.46 63,280.55 2,819.22 2,600.48 291,532.71 33,709.30
1C-3F-4H-33 kV-336.4-AWG-AAC-PC (URBANA) 239,831.18 69,818.07 2,713.09 2,853.25 315,215.59 33,709.30
1C-3F-4H-33 kV-477-AWG-AAC-PC (URBANA) 271,128.21 69,818.07 2,713.09 2,853.25 346,512.62 33,709.30
1C-3F-3H 33 KV 477 AWG AAC-PC URBANA 254,129.49 63,280.55 2,819.22 2,600.48 322,829.74 33,709.30
1C-3F-3H-33 KV-477-AWG-ACSR-PC (URBANA) 324,866.72 140,296.88 2,819.22 2,600.48 470,583.30 33,709.30
1C-3F-3H 33 KV 250 AWG Cu-PC URBANA 1,021,608.77 63,280.55 2,819.22 2,600.48 1,090,309.01 33,709.30

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 961.33
Costo por conexión de línea de 2 fases : $ 1,272.79
Costo por conexión de línea de 3 fases : $ 1,618.17

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (urbana-semiaislado) Poste de Madera
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-3F-4H-13 kV-3/0-AWG-SA-ACSR-PM (URBANA) 280,385.08 75,181.15 2,819.22 2,853.25 361,238.70 33,709.30
1C-3F-4H-13 kV-3/0-AWG-SA-AAC-PM (URBANA) 267,702.43 75,181.15 2,819.22 2,853.25 348,556.05 33,709.30
1C-3F-4H-13 kV-266.8-AWG-SA-AAC-PM (URBANA) 291,232.30 75,181.15 2,819.22 2,853.25 372,085.91 33,709.30
1C-3F-4H-13 kV-266.8-AWG-SA-ACSR-PM (URBANA) 354,968.69 75,181.15 2,819.22 2,853.25 435,822.31 33,709.30
1C-3F-4H-13 kV-336.4-AWG-SA-AAC-PM (URBANA) 319,626.90 75,181.15 2,819.22 2,853.25 400,480.51 33,709.30
1C-3F-4H-13 kV-336.4-AWG-SA-ACSR-PM (URBANA) 378,677.99 75,181.15 2,819.22 2,853.25 459,531.60 33,709.30
1C-3F-4H-23 kV-3/0-AWG-SA-AAC-PM (URBANA) 295,973.32 75,181.15 2,819.22 2,853.25 376,826.93 33,709.30
1C-3F-4H-23 kV-3/0-AWG-SA-ACSR-PM (URBANA) 312,129.57 75,181.15 2,819.22 2,853.25 392,983.18 33,709.30
1C-3F-4H-23 kV-266.8-AWG-SA-AAC-PM (URBANA) 334,923.78 75,181.15 2,819.22 2,853.25 415,777.39 33,709.30
1C-3F-4H-23 kV-266.8-AWG-SA-ACSR-PM (URBANA) 367,640.18 75,181.15 2,819.22 2,853.25 448,493.79 33,709.30
1C-3F-4H-23 kV-336.4-AWG-SA-AAC-PM (URBANA) 382,301.97 75,181.15 2,819.22 2,853.25 463,155.59 33,709.30
1C-3F-4H-23 kV-336.4-AWG-SA-ACSR-PM (URBANA) 382,301.97 75,181.15 2,819.22 2,853.25 463,155.59 33,709.30
1C-3F-4H-33 kV-3/0-AWG-SA-AAC-PM (URBANA) 350,672.20 75,181.15 2,819.22 2,853.25 431,525.81 33,709.30
1C-3F-4H-33 kV-3/0-AWG-SA-ACSR-PM (URBANA) 346,511.96 75,181.15 2,819.22 2,853.25 427,365.58 33,709.30
1C-3F-4H-33 kV-266.8-AWG-SA-AAC-PM (URBANA) 365,869.07 75,181.15 2,819.22 2,853.25 446,722.69 33,709.30
1C-3F-4H-33 kV-266.8-AWG-SA-ACSR-PM (URBANA) 407,107.90 75,181.15 2,819.22 2,853.25 487,961.51 33,709.30
1C-3F-4H-33 kV-336.4-AWG-SA-ACSR-PM (URBANA) 435,623.68 75,181.15 2,819.22 2,853.25 516,477.29 33,709.30
1C-3F-4H-33 kV-366.4-AWG-SA-AAC-PM (URBANA) 415,226.42 75,181.15 2,819.22 2,853.25 496,080.03 33,709.30

icoNotasNota:
Estos costos no incluyen IVA
Costos por conexión de línea : $ 1,699.62

Precios a enero del 2014 M.N.
 
Por kilometro de línea de distribución aerea (urbana-semiaislado) Poste de Concerto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-3F-3H 13 KV 1/0 AWG SA-AAC-PC URBANA 233,572.68 70,277.76 2,819.22 2,600.48 309,270.14 33,709.30
1C-3F-4H-13 kV-3/0-AWG-SA-AAC-PC (URBANA) 268,559.24 76,815.28 2,819.22 2,853.25 351,046.98 33,709.30
1C-3F-4H-13 kV-3/0-AWG-SA-ACSR-PC (URBANA) 281,241.90 76,815.28 2,819.22 2,853.25 363,729.65 33,709.30
1C-3F-3H 13 KV 3/0 AWG SA-AAC-PC URBANA 249,971.27 70,277.76 2,819.22 2,600.48 325,668.73 33,709.30
1C-3F-3H 13 KV 266 AWG SA-AAC-PC URBANA 305,710.33 70,277.76 2,819.22 2,600.48 381,407.79 33,709.30
1C-3F-4H-13 kV-266.8-AWG-SA-AAC-PC (URBANA) 290,370.18 76,815.28 2,819.22 2,853.25 372,857.92 33,709.30
1C-3F-4H-13 kV-266.8-AWG-SA-ACSR-PC (URBANA) 354,106.58 76,815.28 2,819.22 2,853.25 436,594.33 33,709.30
1C-3F-3H 13 KV 336 AWG SA-AAC-PC URBANA 356,319.78 70,277.76 2,819.22 2,600.48 432,017.24 33,709.30
1C-3F-4H-13 kV-336.4-AWG-SA-AAC-PC (URBANA) 318,764.78 76,815.28 2,819.22 2,853.25 401,252.53 33,709.30
1C-3F-4H-13 kV-336.4-AWG-SA-ACSR-PC (URBANA) 377,815.88 76,815.28 2,819.22 2,853.25 460,303.62 33,709.30
1C-3F-3H 23 KV 1/0 AWG SA-AAC-PC URBANA 284,822.81 70,277.76 2,819.22 2,600.48 360,520.27 33,709.30
1C-3F-3H 23 KV 3/0 AWG SA-AAC-PC URBANA 289,669.69 70,277.76 2,819.22 2,600.48 365,367.15 33,709.30
1C-3F-4H-23 kV-3/0-AWG-SA-AAC-PC (URBANA) 308,257.66 76,815.28 2,819.22 2,853.25 390,745.41 33,709.30
1C-3F-4H-23 kV-3/0-AWG-SA-ACSR-PC (URBANA) 324,413.91 76,815.28 2,819.22 2,853.25 406,901.66 33,709.30
1C-3F-3H 23 KV 266 AWG SA-AAC-PC URBANA 326,829.06 70,277.76 2,819.22 2,600.48 402,526.52 33,709.30
1C-3F-4H-23 kV-266.8-AWG-SA-AAC-PC (URBANA) 345,417.03 76,815.28 2,819.22 2,853.25 427,904.78 33,709.30
1C-3F-4H-23 kV-266.8-AWG-SA-ACSR-PC (URBANA) 378,133.43 76,815.28 2,819.22 2,853.25 460,621.18 33,709.30
1C-3F-3H 23 KV 336 AWG SA-AAC-PC URBANA 374,207.27 70,277.76 2,819.22 2,600.48 449,904.72 33,709.30
1C-3F-4H-23 kV-336.4-AWG-SA-AAC-PC (URBANA) 392,795.23 76,815.28 2,819.22 2,853.25 475,282.97 33,709.30
1C-3F-4H-23 kV-336.4-AWG-SA-ACSR-PC (URBANA) 392,795.23 76,815.28 2,819.22 2,853.25 475,282.97 33,709.30
1C-3F-3H 33 KV 1/0 AWG SA-AAC-PC URBANA 322,620.19 70,277.76 2,819.22 2,600.48 398,317.65 33,709.30
1C-3F-4H-33 kV-3/0-AWG-SA-AAC-PC (URBANA) 334,085.39 76,815.28 2,713.09 2,853.25 416,467.01 33,709.30
1C-3F-4H-33 kV-3/0-AWG-SA-ACSR-PC (URBANA) 329,925.16 76,815.28 2,713.09 2,853.25 412,306.78 33,709.30
1C-3F-3H 33 KV 3/0 AWG SA-AAC-PC URBANA 317,086.68 70,277.76 2,819.22 2,600.48 392,784.14 33,709.30
1C-3F-4H-33 kV-266.8-AWG-SA-AAC-PC (URBANA) 347,414.30 76,815.28 2,713.09 2,853.25 429,795.92 33,709.30
1C-3F-4H-33 kV-266.8-AWG-SA-ACSR-PC (URBANA) 388,653.13 76,815.28 2,713.09 2,853.25 471,034.75 33,709.30
1C-3F-3H 33 KV 266 AWG SA-AAC-PC URBANA 330,415.58 70,277.76 2,819.22 2,600.48 406,113.04 33,709.30
1C-3F-4H-33 kV-336.4-AWG-SA-ACSR-PC (URBANA) 417,168.91 76,815.28 2,713.09 2,853.25 499,550.53 33,709.30
1C-3F-4H-33 kV-366.4-AWG-SA-AAC-PC (URBANA) 396,771.64 76,815.28 2,713.09 2,853.25 479,153.26 33,709.30
1C-3F-3H 33 KV 336 AWG SA-AAC-PC URBANA 379,772.93 70,277.76 2,819.22 2,600.48 455,470.39 33,709.30

icoNotasNota:
Estos costos no incluyen IVA
Costos por conexión de línea : $ 1,699.62