Costo de construcción de redes aereas

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (rural) Poste de Madera
Descripción Materiales y equipo de instalación permanente
($)
Mano de obra
($)
Diseño del proyecto
($)
Supervision
($)
Costo total /Km
($)
Retiro
($)
1C-1F-2H-13 kV-1/0-AWG-ACSR-PM (RURAL) 73,077.70 36,152.52 1,664.68 1,580.40 112,475.30 18,524.53
1C-1F-2H-13 kV-3/0-AWG-ACSR-PM (RURAL) 78,875.27 63,085.59 1,664.68 1,580.40 145,205.93 18,524.53
1C-1F-2H-13 kV-266.8-AWG-ACSR-PM (RURAL) 97,065.43 63,085.59 1,664.68 1,580.40 163,396.09 18,524.53
1C-1F-2H-23 kV-1/0-AWG-ACSR-PM (RURAL) 73,929.63 36,152.52 1,664.68 1,580.40 113,327.22 18,524.53
1C-1F-2H-23 kV-3/0-AWG-ACSR-PM (RURAL) 79,727.18 63,085.59 1,664.68 1,580.40 146,057.85 18,524.53
1C-1F-2H-23 kV-266.8-AWG-ACSR-PM (RURAL) 97,917.35 63,085.59 1,664.68 1,580.40 164,248.01 18,524.53
1C-1F-2H-33 kV-1/0-AWG-ACSR-PM (RURAL) 77,700.40 36,152.52 1,664.68 1,580.40 117,097.99 18,524.53
1C-1F-2H-33 kV-3/0-AWG-ACSR-PM (RURAL) 83,497.96 63,085.59 1,664.68 1,580.40 149,828.63 18,524.53
1C-1F-2H-33 kV-266.8-AWG-ACSR-PM (RURAL) 101,688.12 63,085.59 1,664.68 1,580.40 168,018.79 18,524.53
1C-2F-3H-13 kV-1/0-2-AWG-CU-PM (RURAL) 322,354.49 41,656.57 1,664.68 1,845.59 367,521.33 18,524.53
1C-2F-3H-13 kV-1/0-AWG-ACSR-PM (RURAL) 97,601.96 40,662.95 1,664.68 1,845.59 141,775.18 18,524.53
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PM (RURAL) 470,501.09 42,125.41 1,664.68 1,845.59 516,136.77 18,524.53
1C-2F-3H-13 kV-3/0-AWG-ACSR-PM (RURAL) 109,197.08 94,529.08 1,664.68 1,845.59 207,236.43 18,524.53
1C-2F-3H-13 kV-2-AWG-CU-PM (RURAL) 249,374.18 40,662.95 1,664.68 1,845.59 293,547.40 18,524.53
1C-2F-3H-13 kV-266.8-AWG-ACSR-PM (RURAL) 147,297.33 94,585.03 1,664.68 1,845.59 245,392.63 18,524.53
1C-2F-3H-23 kV-1/0-AWG-ACSR-PM (RURAL) 99,218.04 40,662.95 2,036.47 1,845.59 143,763.05 18,524.53
1C-2F-3H-23 kV-3/0-AWG-ACSR-PM (RURAL) 110,813.16 94,529.08 2,036.47 1,845.59 209,224.30 18,524.53
1C-2F-3H-23 kV-266.8-AWG-ACSR-PM (RURAL) 148,913.41 94,585.03 1,664.68 1,845.59 247,008.71 18,524.53
1C-2F-3H-33 kV-1/0-AWG-ACSR-PM (RURAL) 107,797.12 40,662.95 1,664.68 1,845.59 151,970.33 18,524.53
1C-2F-3H-33 kV-3/0-AWG-ACSR-PM (RURAL) 119,392.23 94,529.08 1,664.68 1,845.59 217,431.59 18,524.53
1C-2F-3H-33 kV-266.8-AWG-ACSR-PM (RURAL) 157,492.49 94,585.03 1,664.68 1,845.59 255,587.79 18,524.53
1C-3F-4H-13 kV-1/0-2-AWG-CU-PM (RURAL) 424,419.83 46,835.05 1,664.68 2,110.79 475,030.35 18,524.53
1C-3F-4H-13 kV-1/0-AWG-ACSR-PM (RURAL) 113,432.56 45,428.54 1,664.68 2,110.79 162,636.56 18,524.53
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PM (RURAL) 628,824.64 47,303.90 1,664.68 2,110.79 679,904.00 18,524.53
1C-3F-4H-13 kV-3/0-AWG-ACSR-PM (RURAL) 130,825.23 126,227.76 1,664.68 2,110.79 260,828.46 18,524.53
1C-3F-4H-13 kV-2-AWG-CU-PM (RURAL) 315,795.51 45,428.54 1,664.68 2,110.79 364,999.52 18,524.53
1C-3F-4H-13 kV-266.8-AWG-ACSR-PM (RURAL) 187,129.46 126,227.76 1,664.68 2,110.79 317,132.69 18,524.53
1C-3F-4H-13 kV-336.4-AWG-ACSR-PM (RURAL) 211,239.94 127,634.27 1,664.68 2,110.79 342,649.68 18,524.53
1C-3F-4H-13 kV-477-AWG-ACSR-PM (RURAL) 269,097.46 127,746.51 1,599.64 2,097.62 400,541.23 18,524.53
1C-3F-4H-23 kV-1/0-AWG-ACSR-PM (RURAL) 115,783.88 45,428.54 1,664.68 2,110.79 164,987.89 18,524.53
1C-3F-4H-23 kV-3/0-AWG-ACSR-PM (RURAL) 133,176.55 126,227.76 1,664.68 2,110.79 263,179.78 18,524.53
1C-3F-4H-23 kV-266.8-AWG-ACSR-PM (RURAL) 189,553.57 126,227.76 1,664.68 2,110.79 319,556.80 18,524.53
1C-3F-4H-23 kV-336.4-AWG-ACSR-PM (RURAL) 213,664.05 127,634.27 1,664.68 2,110.79 345,073.79 18,524.53
1C-3F-4H-23 kV-477-AWG-ACSR-PM (RURAL) 271,114.36 127,746.51 1,599.64 2,097.62 402,558.13 18,524.53
1C-3F-4H-33 kV-1/0-AWG-ACSR-PM (RURAL) 130,256.70 39,224.44 1,664.68 2,110.79 173,256.60 19,776.78
1C-3F-4H-33 kV-3/0-AWG-ACSR-PM (RURAL) 145,765.30 126,227.76 1,664.68 2,110.79 275,768.53 19,776.78
1C-3F-4H-33 kV-266.8-AWG-ACSR-PM (RURAL) 202,219.86 126,227.76 1,664.68 2,110.79 332,223.09 19,776.78
1C-3F-4H-33 kV-336.4-AWG-ACSR-PM (RURAL) 226,330.34 127,634.27 1,664.68 2,110.79 357,740.08 19,776.78
1C-3F-4H-33 kV-477-AWG-ACSR-PM (RURAL) 282,832.57 127,746.51 1,599.64 2,097.62 414,276.34 18,524.53

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,537.93
Costo por conexión de línea de 2 fases : $ 1,965.13
Costo por conexión de línea de 3 fases : $ 2,227.02

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (rural) Poste de Concreto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PC (RURAL) 79,095.00 37,048.52 1,599.64 1,567.23 119,310.39 18,524.53
1C-1F-2H-13 kV-3/0-AWG-ACSR-PC (RURAL) 84,892.55 63,981.60 1,599.64 1,567.23 152,041.02 18,524.53
1C-1F-2H-13 kV-266.8-AWG-ACSR-PC (RURAL) 103,082.72 63,981.60 1,599.64 1,567.23 170,231.19 18,524.53
1C-1F-2H-23 kV-1/0-AWG-ACSR-PC (RURAL) 81,888.71 37,048.52 1,599.64 1,567.23 122,104.10 18,524.53
1C-1F-2H-23 kV-3/0-AWG-ACSR-PC (RURAL) 87,686.27 63,981.60 1,599.64 1,567.23 154,834.74 18,524.53
1C-1F-2H-23 kV-266.8-AWG-ACSR-PC (RURAL) 105,876.43 63,981.60 1,599.64 1,567.23 173,024.90 18,524.53
1C-1F-2H-33 kV-1/0-AWG-ACSR-PC (RURAL) 82,464.99 37,048.52 1,599.64 1,567.23 122,680.38 18,524.53
1C-1F-2H-33 kV-3/0-AWG-ACSR-PC (RURAL) 88,262.54 63,981.60 1,599.64 1,567.23 155,411.01 18,524.53
1C-1F-2H-33 kV-266.8-AWG-ACSR-PC (RURAL) 106,452.71 63,981.60 1,599.64 1,567.23 173,601.18 18,524.53
1C-2F-3H-13 kV-1/0-2-AWG-CU-PC (RURAL) 316,363.94 42,552.57 1,599.64 1,832.43 362,348.58 18,524.53
1C-2F-3H-13 kV-1/0-AWG-ACSR-PC (RURAL) 93,331.34 41,614.90 1,599.64 1,832.43 138,378.30 18,524.53
1C-2F-2H 13 KV 1/0 AWG AAC-PC RURAL 71,322.68 35,334.13 1,599.64 1,567.23 109,823.67 18,524.53
1C-2F-2H 13 KV 1/0 AWG ACSR-PC RURAL 76,611.36 35,334.13 1,599.64 1,567.23 115,112.36 18,524.53
1C-2F-2H 13 KV 1/0 AWG Cu-PC RURAL 249,053.22 36,271.81 1,599.64 1,567.23 288,491.90 18,524.53
1C-2F-2H 13 KV 3/0 AWG AAC-PC RURAL 79,638.44 35,334.13 1,599.64 1,567.23 118,139.44 18,524.53
1C-2F-2H 13 KV 3/0 AWG ACSR-PC RURAL 88,206.47 89,200.27 1,599.64 1,567.23 180,573.61 18,524.53
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PC (RURAL) 464,510.54 43,021.42 1,599.64 1,832.43 510,964.02 18,524.53
1C-2F-3H-13 kV-3/0-AWG-ACSR-PC (RURAL) 104,926.45 95,481.04 1,599.64 1,832.43 203,839.56 18,524.53
1C-2F-3H-13 kV-2-AWG-CU-PC (RURAL) 245,103.55 41,614.90 1,599.64 1,832.43 290,150.52 18,524.53
1C-2F-3H-13 kV-266.8-AWG-ACSR-PC (RURAL) 141,306.78 95,481.04 1,599.64 1,832.43 240,219.88 18,524.53
1C-2F-2H 13 KV 2 AWG Cu-PC RURAL 177,792.83 35,334.13 1,599.64 1,567.23 216,293.83 18,524.53
1C-2F-3H-23 kV-1/0-AWG-ACSR-PC (RURAL) 98,948.75 41,614.90 1,599.64 1,832.43 143,995.72 18,524.53
1C-2F-3H-23 kV-3/0-AWG-ACSR-PC (RURAL) 110,543.86 95,481.04 1,599.64 1,832.43 209,456.96 18,524.53
1C-2F-3H-23 kV-266.8-AWG-ACSR-PC (RURAL) 146,924.20 95,481.04 1,599.64 1,832.43 245,837.30 18,524.53
1C-2F-3H-33 kV-1/0-AWG-ACSR-PC (RURAL) 97,398.07 41,614.90 1,599.64 1,832.43 142,445.03 18,524.53
1C-2F-3H-33 kV-3/0-AWG-ACSR-PC (RURAL) 108,993.18 95,481.04 1,599.64 1,832.43 207,906.29 18,524.53
1C-2F-3H-33 kV-266.8-AWG-ACSR-PC (RURAL) 145,373.51 95,481.04 1,599.64 1,832.43 244,286.61 18,524.53
1C-3F-3H-13 KV-1/0-AWG-ACSR-PC (RURAL) 93,079.90 39,900.51 1,599.64 1,832.43 136,412.47 18,524.53
1C-3F-3H 13 KV 1/0 AWG AAC-PC RURAL 85,146.87 39,900.51 1,599.64 1,832.43 128,479.44 18,524.53
1C-3F-3H 13 KV 1/0 AWG SA-AAC-PC RURAL 168,057.72 48,647.92 1,599.64 1,832.43 220,137.71 18,524.53
1C-3F-4H-13 kV-1/0-2-AWG-CU-PC (RURAL) 417,350.55 47,731.07 1,599.64 2,097.62 468,778.88 18,524.53
1C-3F-4H-13 kV-1/0-AWG-ACSR-PC (RURAL) 108,097.02 46,324.56 1,599.64 2,097.62 158,118.84 18,524.53
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PC (RURAL) 621,755.35 48,199.90 1,599.64 2,097.62 673,652.51 18,524.53
1C-3F-4H-13 kV-3/0-AWG-ACSR-PC (RURAL) 125,489.69 127,123.77 1,599.64 2,097.62 256,310.72 18,524.53
1C-3F-3H-13 KV-3/0-AWG-ACSR-PC (RURAL) 110,472.56 120,699.71 1,599.64 1,832.43 234,604.34 18,524.53
1C-3F-3H 13 KV 3/0 AWG AAC-PC RURAL 97,620.51 39,900.51 1,599.64 1,832.43 140,953.08 18,524.53
1C-3F-3H 13 KV 3/0 AWG SA-AAC-PC RURAL 184,597.63 48,647.92 1,599.64 1,832.43 236,677.62 18,524.53
1C-3F-3H-13 KV-266.8-AWG-ACSR-PC (RURAL) 165,043.05 120,699.71 1,599.64 1,832.43 289,174.83 18,524.53
1C-3F-3H 13 KV 266 AWG AAC-PC RURAL 121,217.84 39,900.51 1,599.64 1,832.43 164,550.41 18,524.53
1C-3F-3H 13 KV 266 AWG SA-AAC-PC RURAL 240,817.03 48,647.92 1,599.64 1,832.43 292,897.02 18,524.53
1C-3F-4H-13 kV-2-AWG-CU-PC (RURAL) 310,459.96 46,324.56 1,599.64 2,097.62 360,481.79 18,524.53
1C-3F-4H-13 kV-266.8-AWG-ACSR-PC (RURAL) 180,060.19 127,123.77 1,599.64 2,097.62 310,881.22 18,524.53
1C-3F-4H-13 kV-336.4-AWG-ACSR-PC (RURAL) 204,170.66 128,530.28 1,599.64 2,097.62 336,398.20 18,524.53
1C-3F-3H-13 KV-336.4-AWG-ACSR-PC (RURAL) 189,153.54 122,106.23 1,599.64 1,832.43 314,691.83 18,524.53
1C-3F-3H 13 KV 336 AWG AAC-PC RURAL 140,169.36 41,307.02 1,599.64 1,832.43 184,908.45 18,524.53
1C-3F-3H 13 KV 336 AWG SA-AAC-PC RURAL 291,862.62 48,647.92 1,599.64 1,832.43 343,942.61 18,524.53
1C-3F-3H 13 KV 477 AWG AAC-PC RURAL 171,736.10 41,307.02 1,599.64 1,832.43 216,475.19 18,524.53
1C-3F-3H-13 KV-477-AWG-ACSR-PC (RURAL) 243,082.93 122,106.23 1,599.64 1,832.43 368,621.22 18,524.53
1C-3F-4H-13 kV-477-AWG-ACSR-PC (RURAL) 258,100.05 128,530.28 1,599.64 2,097.62 390,327.59 18,524.53
1C-3F-4H-23 kV-1/0-AWG-ACSR-PC (RURAL) 117,525.79 46,324.56 1,599.64 2,097.62 167,547.61 18,524.53
1C-3F-3H-23 KV-1/0-AWG-ACSR-PC (RURAL) 100,393.33 39,900.51 1,599.64 1,832.43 143,725.90 18,524.53
1C-3F-3H 23 KV 1/0 AWG AAC-PC RURAL 92,460.30 39,900.51 1,599.64 1,832.43 135,792.87 18,524.53
1C-3F-3H 23 KV 1/0 AWG SA-AAC-PC RURAL 209,021.33 48,647.92 1,599.64 1,832.43 261,101.31 18,524.53
1C-3F-3H 23 KV 3/0 AWG AAC-PC RURAL 104,933.94 39,900.51 1,599.64 1,832.43 148,266.52 18,524.53
1C-3F-3H 23 KV 3/0 AWG SA-AAC-PC RURAL 213,909.97 48,647.92 1,599.64 1,832.43 265,989.96 18,524.53
1C-3F-3H-23 KV-3/0-AWG-ACSR-PC (RURAL) 117,786.00 120,699.71 1,599.64 1,832.43 241,917.78 18,524.53
1C-3F-4H-23 kV-3/0-AWG-ACSR-PC (RURAL) 134,918.46 127,123.77 1,599.64 2,097.62 265,739.49 18,524.53
1C-3F-4H-23 kV-266.8-AWG-ACSR-PC (RURAL) 189,488.95 127,123.77 1,599.64 2,097.62 320,309.98 18,524.53
1C-3F-3H-23 KV-266.8-AWG-ACSR-PC (RURAL) 172,356.50 120,699.71 1,599.64 1,832.43 296,488.28 18,524.53
1C-3F-3H 23 KV 266 AWG AAC-PC RURAL 128,531.28 39,900.51 1,599.64 1,832.43 171,863.85 18,524.53
1C-3F-3H 23 KV 266 AWG SA-AAC-PC RURAL 251,389.57 48,647.92 1,599.64 1,832.43 303,469.56 18,524.53
1C-3F-3H 23 KV 336 AWG AAC-PC RURAL 147,482.81 41,307.02 1,599.64 1,832.43 192,221.89 18,524.53
1C-3F-3H 23 KV 336 AWG SA-AAC-PC RURAL 299,176.06 48,647.92 1,599.64 1,832.43 351,256.04 18,524.53
1C-3F-3H-23 KV-336.4-AWG-ACSR-PC (RURAL) 196,466.97 122,106.23 1,599.64 1,832.43 322,005.26 18,524.53
1C-3F-4H-23 kV-336.4-AWG-ACSR-PC (RURAL) 213,599.44 128,530.28 1,599.64 2,097.62 345,826.98 18,524.53
1C-3F-4H-23 kV-477-AWG-ACSR-PC (RURAL) 267,528.81 128,530.28 1,599.64 2,097.62 399,756.36 18,524.53
1C-3F-3H-23 KV-477-AWG-ACSR-PC (RURAL) 250,396.36 122,106.23 1,599.64 1,832.43 375,934.65 18,524.53
1C-3F-3H 23 KV 477 AWG AAC-PC RURAL 179,049.54 41,307.02 1,599.64 1,832.43 223,788.62 18,524.53
1C-3F-3H 33 KV 1/0 AWG AAC-PC RURAL 92,526.10 39,900.51 1,599.64 1,832.43 135,858.67 18,524.53
1C-3F-3H 33 KV 1/0 AWG SA-AAC-PC RURAL 248,196.28 48,647.92 1,599.64 1,832.43 300,276.26 18,524.53
1C-3F-3H-33 KV-1/0-AWG-ACSR-PC (RURAL) 100,459.13 39,900.51 1,599.64 1,832.43 143,791.70 18,524.53
1C-3F-4H-33 kV-1/0-AWG-ACSR-PC (RURAL) 114,823.39 46,324.56 1,599.64 2,097.62 164,845.21 18,524.53
1C-3F-3H-33 KV-3/0-AWG-ACSR-PC (RURAL) 117,851.80 120,699.71 1,599.64 1,832.43 241,983.58 18,524.53
1C-3F-3H 33 KV 3/0 AWG AAC-PC RURAL 104,999.76 39,900.51 1,599.64 1,832.43 148,332.33 18,524.53
1C-3F-3H 33 KV 3/0 AWG SA-AAC-PC RURAL 242,615.07 48,647.92 1,599.64 1,832.43 294,695.06 18,524.53
1C-3F-4H-33 kV-3/0-AWG-ACSR-PC (RURAL) 132,216.06 127,123.77 1,599.64 2,097.62 263,037.09 18,524.53
1C-3F-3H-33 KV-226.8-AWG-ACSR-PC (RURAL) 172,422.30 120,699.71 1,599.64 1,832.43 296,554.08 18,524.53
1C-3F-3H 33 KV 266 AWG AAC-PC RURAL 128,597.08 39,900.51 1,599.64 1,832.43 171,929.65 18,524.53
1C-3F-3H 33 KV 266 AWG SA-AAC-PC RURAL 256,058.85 48,647.92 1,599.64 1,832.43 308,138.83 18,524.53
1C-3F-4H-33 kV-266.8-AWG-ACSR-PC (RURAL) 186,786.56 127,123.77 1,599.64 2,097.62 317,607.59 18,524.53
1C-3F-3H-33 KV-336.4-AWG-ACSR-PC (RURAL) 196,532.77 122,106.23 1,599.64 1,832.43 322,071.06 18,524.53
1C-3F-3H 33 KV 336 AWG AAC-PC RURAL 147,548.61 41,307.02 1,599.64 1,832.43 192,287.69 18,524.53
1C-3F-3H 33 KV 336 AWG SA-AAC-PC RURAL 305,841.53 48,647.92 1,599.64 1,832.43 357,921.52 18,524.53
1C-3F-4H-33 kV-336.4-AWG-ACSR-PC (RURAL) 210,897.03 128,530.28 1,599.64 2,097.62 343,124.58 18,524.53
1C-3F-4H-33 kV-477-AWG-ACSR-PC (RURAL) 264,826.42 128,530.28 1,599.64 2,097.62 397,053.96 18,524.53
1C-3F-3H 33 KV 477 AWG AAC-PC RURAL 179,115.35 41,307.02 1,599.64 1,832.43 223,854.43 18,524.53
1C-3F-3H-33 KV-477-AWG-ACSR-PC (RURAL) 250,462.16 122,106.23 1,599.64 1,832.43 376,000.45 18,524.53

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,537.93
Costo por conexión de línea de 2 fases : $ 1,965.13
Costo por conexión de línea de 3 fases : $ 2,227.02

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (urbana) Poste de Madera
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PM (URBANA) 120,904.73 58,355.42 2,957.69 2,463.02 184,680.86 35,365.03
1C-1F-2H-13 kV-3/0-AWG-AAC-PM (URBANA) 122,418.27 58,355.42 2,957.69 2,463.02 186,194.39 35,365.03
1C-1F-2H-13 kV-266.8-AWG-AAC-PM (URBANA) 130,284.05 58,355.42 2,957.69 2,463.02 194,060.17 35,365.03
1C-1F-2H-23 kV-1/0-AWG-ACSR-PM (URBANA) 123,355.30 58,299.47 2,957.69 2,463.02 187,075.48 35,365.03
1C-1F-2H-23 kV-3/0-AWG-AAC-PM (URBANA) 124,868.84 58,299.47 2,957.69 2,463.02 188,589.02 35,365.03
1C-1F-2H-23 kV-266.8-AWG-AAC-PM (URBANA) 132,734.62 58,299.47 2,957.69 2,463.02 196,454.80 35,365.03
1C-1F-2H-33 kV-1/0-AWG-ACSR-PM (URBANA) 131,040.90 58,299.47 2,957.69 2,463.02 194,761.07 35,365.03
1C-1F-2H-33 kV-3/0-AWG-AAC-PM (URBANA) 132,554.44 58,299.47 2,957.69 2,463.02 196,274.61 35,365.03
1C-1F-2H-33 kV-266.8-AWG-AAC-PM (URBANA) 140,420.21 58,299.47 2,957.69 2,463.02 204,140.39 35,365.03
1C-2F-3H-13 kV-1/0-2-AWG-CU-PM (URBANA) 385,774.70 65,613.80 2,957.69 2,728.21 457,074.41 35,365.03
1C-2F-3H-13 kV-1/0-AWG-ACSR-PM (URBANA) 161,022.17 64,676.13 2,957.69 2,728.21 231,384.21 35,365.03
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PM (URBANA) 533,921.30 66,082.65 2,957.69 2,728.21 605,689.85 35,365.03
1C-2F-3H-13 kV-3/0-AWG-AAC-PM (URBANA) 164,049.26 64,676.13 2,957.69 2,728.21 234,411.29 35,365.03
1C-2F-3H-13 kV-266.8-AWG-AAC-PM (URBANA) 181,500.73 64,676.13 2,957.69 2,728.21 251,862.77 35,365.03
1C-2F-3H-13 kV-250-1/0-AWG-CU-PM (URBANA) 817,462.64 66,082.65 2,957.69 2,728.21 889,231.19 35,365.03
1C-2F-3H-23 kV-1/0-AWG-ACSR-PM (URBANA) 165,685.91 64,676.13 2,957.69 2,728.21 236,047.95 35,365.03
1C-2F-3H-23 kV-3/0-AWG-AAC-PM (URBANA) 168,713.00 64,676.13 2,957.69 2,728.21 239,075.03 35,365.03
1C-2F-3H-23 kV-266.8-AWG-AAC-PM (URBANA) 186,164.47 64,676.13 2,957.69 2,728.21 256,526.51 35,365.03
1C-2F-3H-33 kV-1/0-AWG-ACSR-PM (URBANA) 183,160.38 64,676.13 2,957.69 2,728.21 253,522.42 35,365.03
1C-2F-3H-33 kV-3/0-AWG-AAC-PM (URBANA) 186,187.47 64,676.13 2,957.69 2,728.21 256,549.50 35,365.03
1C-2F-3H-33 kV-266.8-AWG-AAC-PM (URBANA) 203,638.94 64,676.13 2,957.69 2,728.21 274,000.98 35,365.03
1C-3F-4H-13 kV-1/0-2-AWG-CU-PM (URBANA) 489,478.95 71,532.98 2,957.69 2,993.39 566,963.02 35,365.03
1C-3F-4H-13 kV-1/0-AWG-ACSR-PM (URBANA) 178,491.68 70,126.47 2,957.69 2,993.39 254,569.23 35,365.03
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PM (URBANA) 693,883.75 72,001.82 2,957.69 2,993.39 771,836.66 35,365.03
1C-3F-4H-13 kV-3/0-AWG-AAC-PM (URBANA) 183,032.30 70,126.47 2,957.69 2,993.39 259,109.85 35,365.03
1C-3F-4H-13 kV-266.8-AWG-AAC-PM (URBANA) 208,363.36 70,126.47 2,957.69 2,993.39 284,440.91 35,365.03
1C-3F-4H-13 kV-336.4-AWG-AAC-PM (URBANA) 227,314.89 71,532.98 2,957.69 2,993.39 304,798.95 35,365.03
1C-3F-4H-13 kV-477-AWG-AAC-PM (URBANA) 264,970.61 71,532.98 2,957.69 2,993.39 342,454.68 35,365.03
1C-3F-4H-13 kV-250-1/0-AWG-CU-PM (URBANA) 1,119,195.76 72,001.82 2,957.69 2,993.39 1,197,148.67 35,365.03
1C-3F-4H-23 kV-1/0-AWG-ACSR-PM (URBANA) 185,007.29 70,126.47 2,957.69 2,993.39 261,084.85 35,365.03
1C-3F-4H-23 kV-3/0-AWG-AAC-PM (URBANA) 189,547.92 70,126.47 2,957.69 2,993.39 265,625.47 35,365.03
1C-3F-4H-23 kV-266.8-AWG-AAC-PM (URBANA) 214,951.77 70,126.47 2,957.69 2,993.39 291,029.32 35,365.03
1C-3F-4H-23 kV-336.4-AWG-AAC-PM (URBANA) 233,903.29 71,532.98 2,957.69 2,993.39 311,387.36 35,365.03
1C-3F-4H-23 kV-477-AWG-AAC-PM (URBANA) 271,151.81 71,532.98 2,957.69 2,993.39 348,635.88 35,365.03
1C-3F-4H-33 kV-1/0-AWG-ACSR-PM (URBANA) 211,538.25 70,126.47 2,957.69 2,993.39 287,615.80 35,365.03
1C-3F-4H-33 kV-3/0-AWG-AAC-PM (URBANA) 216,078.87 70,126.47 2,957.69 2,993.39 292,156.43 35,365.03
1C-3F-4H-33 kV-266.8-AWG-AAC-PM (URBANA) 241,560.26 70,126.47 2,957.69 2,993.39 317,637.81 35,365.03
1C-3F-4H-33 kV-336.4-AWG-AAC-PM (URBANA) 260,511.79 71,532.98 2,957.69 2,993.39 337,995.85 35,365.03
1C-3F-4H-33 kV-477-AWG-AAC-PM (URBANA) 295,020.36 71,532.98 2,957.69 2,993.39 372,504.43 35,365.03

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,008.55
Costo por conexión de línea de 2 fases : $ 1,335.31
Costo por conexión de línea de 3 fases : $ 1,697.66

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (urbana) Poste de Concreto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-1F-2H-13 kV-1/0-AWG-ACSR-PC (URBANA) 130,379.93 60,013.86 2,957.69 2,463.02 195,814.50 35,365.03
1C-1F-2H-13 kV-3/0-AWG-AAC-PC (URBANA) 131,893.46 60,013.86 2,957.69 2,463.02 197,328.04 35,365.03
1C-1F-2H-13 kV-266.8-AWG-AAC-PC (URBANA) 139,759.24 60,013.86 2,957.69 2,463.02 205,193.82 35,365.03
1C-1F-2H-23 kV-1/0-AWG-ACSR-PC (URBANA) 135,801.92 60,013.86 2,957.69 2,463.02 201,236.50 35,365.03
1C-1F-2H-23 kV-3/0-AWG-AAC-PC (URBANA) 137,315.46 60,013.86 2,957.69 2,463.02 202,750.03 35,365.03
1C-1F-2H-23 kV-266.8-AWG-AAC-PC (URBANA) 145,181.24 60,013.86 2,957.69 2,463.02 210,615.81 35,365.03
1C-1F-2H-33 kV-1/0-AWG-ACSR-PC (URBANA) 136,651.08 60,013.86 2,957.69 2,463.02 202,085.66 35,365.03
1C-1F-2H-33 kV-3/0-AWG-AAC-PC (URBANA) 138,164.62 60,013.86 2,957.69 2,463.02 203,599.19 35,365.03
1C-1F-2H-33 kV-266.8-AWG-AAC-PC (URBANA) 146,030.40 60,013.86 2,957.69 2,463.02 211,464.97 35,365.03
1C-2F-2H 13 KV 1/0 AWG AAC-PC URBANA 133,733.42 60,119.34 2,957.69 2,463.02 199,273.46 35,365.03
1C-2F-2H 13 KV 1/0 AWG ACSR-PC URBANA 139,022.10 60,119.34 2,957.69 2,463.02 204,562.15 35,365.03
1C-2F-2H 13 KV 1/0 AWG Cu-PC URBANA 150,617.21 113,985.48 2,957.69 2,463.02 270,023.40 35,365.03
1C-2F-3H-13 kV-1/0-2-AWG-CU-PC (URBANA) 378,799.71 67,328.20 2,957.69 2,728.21 451,813.82 35,365.03
1C-2F-3H-13 kV-1/0-AWG-ACSR-PC (URBANA) 155,767.12 66,390.53 2,957.69 2,728.21 227,843.55 35,365.03
1C-2F-2H 13 KV 3/0 AWG AAC-PC URBANA 142,049.18 60,119.34 2,957.69 2,463.02 207,589.22 35,365.03
1C-2F-2H 13 KV 3/0 AWG ACSR-PC URBANA 150,617.21 113,985.48 2,957.69 2,463.02 270,023.40 35,365.03
1C-2F-3H-13 kV-3/0-1/0-AWG-CU-PC (URBANA) 526,946.31 67,797.04 2,957.69 2,728.21 600,429.26 35,365.03
1C-2F-3H-13 kV-3/0-AWG-AAC-PC (URBANA) 158,794.20 66,390.53 2,957.69 2,728.21 230,870.63 35,365.03
1C-2F-3H-13 kV-266.8-AWG-AAC-PC (URBANA) 174,525.74 66,390.53 2,957.69 2,728.21 246,602.18 35,365.03
1C-2F-3H-13 kV-250-1/0-AWG-CU-PC (URBANA) 810,487.65 67,797.04 2,957.69 2,728.21 883,970.60 35,365.03
1C-2F-2H 13 KV 2 AWG Cu-PC URBANA 240,203.58 60,119.34 2,957.69 2,463.02 305,743.63 35,365.03
1C-2F-3H-23 kV-1/0-AWG-ACSR-PC (URBANA) 167,986.42 66,390.53 2,957.69 2,728.21 240,062.86 35,365.03
1C-2F-3H-23 kV-3/0-AWG-AAC-PC (URBANA) 171,013.50 66,390.53 2,957.69 2,728.21 243,089.93 35,365.03
1C-2F-3H-23 kV-266.8-AWG-AAC-PC (URBANA) 186,745.06 66,390.53 2,957.69 2,728.21 258,821.49 35,365.03
1C-2F-3H-33 kV-1/0-AWG-ACSR-PC (URBANA) 165,674.10 66,390.53 2,957.69 2,728.21 237,750.53 35,365.03
1C-2F-3H-33 kV-3/0-AWG-AAC-PC (URBANA) 168,701.18 66,390.53 2,957.69 2,728.21 240,777.61 35,365.03
1C-2F-3H-33 kV-266.8-AWG-AAC-PC (URBANA) 184,432.72 66,390.53 2,957.69 2,728.21 256,509.16 35,365.03
1C-3F-3H 13 KV 1/0 AWG AAC-PC URBANA 152,674.69 64,982.23 2,957.69 2,728.21 223,342.83 35,365.03
1C-3F-3H 13 KV 1/0 AWG Cu-PC URBANA 419,270.51 66,388.75 2,957.69 2,728.21 491,345.16 35,365.03
1C-3F-3H-13 KV-1/0-AWG-ACSR-PC (URBANA) 160,607.71 64,982.23 2,957.69 2,728.21 231,275.85 35,365.03
1C-3F-4H-13 kV-1/0-2-AWG-CU-PC (URBANA) 488,609.40 73,247.38 2,957.69 2,993.39 567,807.87 35,365.03
1C-3F-4H-13 kV-1/0-AWG-ACSR-PC (URBANA) 179,355.86 71,840.86 2,957.69 2,993.39 257,147.81 35,365.03
1C-3F-4H-13 kV-3/0-1/0-AWG-CU-PC (URBANA) 693,014.20 73,716.22 2,957.69 2,993.39 772,681.51 35,365.03
1C-3F-4H-13 kV-3/0-AWG-AAC-PC (URBANA) 183,896.49 71,840.86 2,957.69 2,993.39 261,688.44 35,365.03
1C-3F-3H-13 KV-3/0-AWG-ACSR-PC (URBANA) 178,000.38 145,781.44 2,957.69 2,728.21 329,467.72 35,365.03
1C-3F-3H 13 KV 3/0 AWG AAC-PC URBANA 165,148.33 64,982.23 2,957.69 2,728.21 235,816.47 35,365.03
1C-3F-3H 13 KV 3/0 AWG Cu-PC URBANA 588,045.11 66,388.75 2,957.69 2,728.21 660,119.77 35,365.03
1C-3F-3H-13 KV-266.8-AWG-ACSR-PC (URBANA) 232,570.87 145,781.44 2,957.69 2,728.21 384,038.22 35,365.03
1C-3F-3H 13 KV 266 AWG AAC-PC URBANA 188,745.66 64,982.23 2,957.69 2,728.21 259,413.80 35,365.03
1C-3F-4H-13 kV-266.8-AWG-AAC-PC (URBANA) 207,493.81 71,840.86 2,957.69 2,993.39 285,285.76 35,365.03
1C-3F-4H-13 kV-336.4-AWG-AAC-PC (URBANA) 226,445.34 73,247.38 2,957.69 2,993.39 305,643.80 35,365.03
1C-3F-3H 13 KV 336 AWG AAC-PC URBANA 207,697.18 66,388.75 2,957.69 2,728.21 279,771.84 35,365.03
1C-3F-3H-13 KV-336.4-AWG-ACSR-PC (URBANA) 256,681.36 147,187.96 2,957.69 2,728.21 409,555.22 35,365.03
1C-3F-3H-13 KV-477-AWG-ACSR-PC (URBANA) 310,610.75 147,187.96 2,957.69 2,728.21 463,484.61 35,365.03
1C-3F-3H 13 KV 477 AWG AAC-PC URBANA 239,263.92 66,388.75 2,957.69 2,728.21 311,338.58 35,365.03
1C-3F-4H-13 kV-477-AWG-AAC-PC (URBANA) 258,012.08 73,247.38 2,957.69 2,993.39 337,210.54 35,365.03
1C-3F-3H 13 KV 250 AWG Cu-PC URBANA 1,013,357.12 66,388.75 2,957.69 2,728.21 1,085,431.77 35,365.03
1C-3F-4H-13 kV-250-1/0-AWG-CU-PC (URBANA) 1,118,326.21 73,716.22 2,957.69 2,993.39 1,197,993.52 35,365.03
1C-3F-3H-23 KV-1/0-AWG-ACSR-PC (URBANA) 178,649.34 64,982.23 2,957.69 2,728.21 249,317.48 35,365.03
1C-3F-3H 23 KV 1/0 AWG AAC-PC URBANA 170,716.31 64,982.23 2,957.69 2,728.21 241,384.45 35,365.03
1C-3F-3H 23 KV 1/0 AWG Cu-PC URBANA 437,312.14 66,388.75 2,957.69 2,728.21 509,386.79 35,365.03
1C-3F-4H-23 kV-1/0-AWG-ACSR-PC (URBANA) 197,397.50 71,840.86 2,957.69 2,993.39 275,189.45 35,365.03
1C-3F-4H-23 kV-3/0-AWG-AAC-PC (URBANA) 201,938.11 71,840.86 2,957.69 2,993.39 279,730.06 35,365.03
1C-3F-3H 23 KV 3/0 AWG AAC-PC URBANA 183,189.97 64,982.23 2,957.69 2,728.21 253,858.11 35,365.03
1C-3F-3H 23 KV 3/0 AWG Cu-PC URBANA 606,086.75 66,388.75 2,957.69 2,728.21 678,161.40 35,365.03
1C-3F-3H-23 KV-3/0-AWG-ACSR-PC (URBANA) 196,042.01 145,781.44 2,957.69 2,728.21 347,509.36 35,365.03
1C-3F-3H-23 KV-266.8-AWG-ACSR-PC (URBANA) 250,612.51 145,781.44 2,957.69 2,728.21 402,079.86 35,365.03
1C-3F-3H 23 KV 266 AWG AAC-PC URBANA 206,787.29 64,982.23 2,957.69 2,728.21 277,455.43 35,365.03
1C-3F-4H-23 kV-266.8-AWG-AAC-PC (URBANA) 225,535.45 71,840.86 2,957.69 2,993.39 303,327.40 35,365.03
1C-3F-3H 23 KV 336 AWG AAC-PC URBANA 225,738.82 66,388.75 2,957.69 2,728.21 297,813.47 35,365.03
1C-3F-3H-23 KV-336.4-AWG-ACSR-PC (URBANA) 274,722.98 147,187.96 2,957.69 2,728.21 427,596.84 35,365.03
1C-3F-4H-23 kV-336.4-AWG-AAC-PC (URBANA) 244,486.97 73,247.38 2,957.69 2,993.39 323,685.44 35,365.03
1C-3F-4H-23 kV-477-AWG-AAC-PC (URBANA) 276,053.70 73,247.38 2,957.69 2,993.39 355,252.17 35,365.03
1C-3F-3H-23 KV-477-AWG-ACSR-PC (URBANA) 328,652.37 147,187.96 2,957.69 2,728.21 481,526.23 35,365.03
1C-3F-3H 23 KV 477 AWG AAC-PC URBANA 257,305.55 66,388.75 2,957.69 2,728.21 329,380.20 35,365.03
1C-3F-3H 23 KV 250 AWG Cu-PC URBANA 1,031,398.75 66,388.75 2,957.69 2,728.21 1,103,473.41 35,365.03
1C-3F-3H 33 KV 1/0 AWG AAC-PC URBANA 169,730.27 64,982.23 2,957.69 2,728.21 240,398.41 35,365.03
1C-3F-3H 33 KV 1/0 AWG Cu-PC URBANA 436,326.09 66,388.75 2,957.69 2,728.21 508,400.74 35,365.03
1C-3F-3H-33 KV-1/0-AWG-ACSR-PC (URBANA) 177,663.30 64,982.23 2,957.69 2,728.21 248,331.44 35,365.03
1C-3F-4H-33 kV-1/0-AWG-ACSR-PC (URBANA) 194,808.50 71,840.86 2,846.36 2,993.39 272,489.12 35,365.03
1C-3F-3H-33 KV-3/0-AWG-ACSR-PC (URBANA) 195,055.97 145,781.44 2,957.69 2,728.21 346,523.32 35,365.03
1C-3F-3H 33 KV 3/0 AWG AAC-PC URBANA 182,203.92 64,982.23 2,957.69 2,728.21 252,872.06 35,365.03
1C-3F-3H 33 KV 3/0 AWG Cu-PC URBANA 605,100.70 66,388.75 2,957.69 2,728.21 677,175.35 35,365.03
1C-3F-4H-33 kV-3/0-AWG-AAC-PC (URBANA) 199,349.13 71,840.86 2,846.36 2,993.39 277,029.74 35,365.03
1C-3F-3H 33 KV 266 AWG AAC-PC URBANA 205,801.24 64,982.23 2,957.69 2,728.21 276,469.38 35,365.03
1C-3F-4H-33 kV-266.8-AWG-AAC-PC (URBANA) 222,946.45 71,840.86 2,846.36 2,993.39 300,627.06 35,365.03
1C-3F-3H-33 KV-226.8-AWG-ACSR-PC (URBANA) 249,626.46 145,781.44 2,957.69 2,728.21 401,093.80 35,365.03
1C-3F-3H-33 KV-336.4-AWG-ACSR-PC (URBANA) 273,736.94 147,187.96 2,957.69 2,728.21 426,610.80 35,365.03
1C-3F-3H 33 KV 336 AWG AAC-PC URBANA 224,752.77 66,388.75 2,957.69 2,728.21 296,827.42 35,365.03
1C-3F-4H-33 kV-336.4-AWG-AAC-PC (URBANA) 241,897.98 73,247.38 2,846.36 2,993.39 320,985.10 35,365.03
1C-3F-4H-33 kV-477-AWG-AAC-PC (URBANA) 273,464.72 73,247.38 2,846.36 2,993.39 352,551.85 35,365.03
1C-3F-3H 33 KV 477 AWG AAC-PC URBANA 256,319.51 66,388.75 2,957.69 2,728.21 328,394.16 35,365.03
1C-3F-3H-33 KV-477-AWG-ACSR-PC (URBANA) 327,666.33 147,187.96 2,957.69 2,728.21 480,540.19 35,365.03
1C-3F-3H 33 KV 250 AWG Cu-PC URBANA 1,030,412.70 66,388.75 2,957.69 2,728.21 1,102,487.36 35,365.03

icoNotasNota:
Estos costos no incluyen IVA
Costo por conexión de línea de 1 fase  : $ 1,008.55
Costo por conexión de línea de 2 fases : $ 1,335.31
Costo por conexión de línea de 3 fases : $ 1,697.66

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (urbana-semiaislado) Poste de Madera
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-3F-4H-13 kV-3/0-AWG-SA-ACSR-PM (URBANA) 282,801.36 78,873.88 2,957.69 2,993.39 367,626.33 35,365.03
1C-3F-4H-13 kV-3/0-AWG-SA-AAC-PM (URBANA) 270,009.42 78,873.88 2,957.69 2,993.39 354,834.39 35,365.03
1C-3F-4H-13 kV-266.8-AWG-SA-AAC-PM (URBANA) 293,742.05 78,873.88 2,957.69 2,993.39 378,567.02 35,365.03
1C-3F-4H-13 kV-266.8-AWG-SA-ACSR-PM (URBANA) 358,027.71 78,873.88 2,957.69 2,993.39 442,852.68 35,365.03
1C-3F-4H-13 kV-336.4-AWG-SA-AAC-PM (URBANA) 322,381.35 78,873.88 2,957.69 2,993.39 407,206.32 35,365.03
1C-3F-4H-13 kV-336.4-AWG-SA-ACSR-PM (URBANA) 381,941.33 78,873.88 2,957.69 2,993.39 466,766.29 35,365.03
1C-3F-4H-23 kV-3/0-AWG-SA-AAC-PM (URBANA) 298,523.93 78,873.88 2,957.69 2,993.39 383,348.90 35,365.03
1C-3F-4H-23 kV-3/0-AWG-SA-ACSR-PM (URBANA) 314,819.41 78,873.88 2,957.69 2,993.39 399,644.38 35,365.03
1C-3F-4H-23 kV-266.8-AWG-SA-AAC-PM (URBANA) 337,810.06 78,873.88 2,957.69 2,993.39 422,635.03 35,365.03
1C-3F-4H-23 kV-266.8-AWG-SA-ACSR-PM (URBANA) 370,808.40 78,873.88 2,957.69 2,993.39 455,633.36 35,365.03
1C-3F-4H-23 kV-336.4-AWG-SA-AAC-PM (URBANA) 385,596.54 78,873.88 2,957.69 2,993.39 470,421.51 35,365.03
1C-3F-4H-23 kV-336.4-AWG-SA-ACSR-PM (URBANA) 385,596.54 78,873.88 2,957.69 2,993.39 470,421.51 35,365.03
1C-3F-4H-33 kV-3/0-AWG-SA-AAC-PM (URBANA) 353,694.19 78,873.88 2,957.69 2,993.39 438,519.16 35,365.03
1C-3F-4H-33 kV-3/0-AWG-SA-ACSR-PM (URBANA) 349,498.11 78,873.88 2,957.69 2,993.39 434,323.07 35,365.03
1C-3F-4H-33 kV-266.8-AWG-SA-AAC-PM (URBANA) 369,022.03 78,873.88 2,957.69 2,993.39 453,847.00 35,365.03
1C-3F-4H-33 kV-266.8-AWG-SA-ACSR-PM (URBANA) 410,616.24 78,873.88 2,957.69 2,993.39 495,441.21 35,365.03
1C-3F-4H-33 kV-336.4-AWG-SA-ACSR-PM (URBANA) 439,377.76 78,873.88 2,957.69 2,993.39 524,202.72 35,365.03
1C-3F-4H-33 kV-366.4-AWG-SA-AAC-PM (URBANA) 418,804.72 78,873.88 2,957.69 2,993.39 503,629.69 35,365.03

icoNotasNota:
Estos costos no incluyen IVA
Costos por conexión de línea : $ 1,783.10

Precios a enero del 2015 M.N.
 
Por kilometro de línea de distribución aerea (urbana-semiaislado) Poste de Concerto
Descripción Materiales y equipo de instalación permanente Mano de obra Diseño del proyecto Supervision Costo total /Km Retiro
1C-3F-3H 13 KV 1/0 AWG SA-AAC-PC URBANA 235,585.54 73,729.65 2,957.69 2,728.21 315,001.10 35,365.03
1C-3F-4H-13 kV-3/0-AWG-SA-AAC-PC (URBANA) 270,873.61 80,588.28 2,957.69 2,993.39 357,412.97 35,365.03
1C-3F-4H-13 kV-3/0-AWG-SA-ACSR-PC (URBANA) 283,665.56 80,588.28 2,957.69 2,993.39 370,204.93 35,365.03
1C-3F-3H 13 KV 3/0 AWG SA-AAC-PC URBANA 252,125.45 73,729.65 2,957.69 2,728.21 331,541.00 35,365.03
1C-3F-3H 13 KV 266 AWG SA-AAC-PC URBANA 308,344.85 73,729.65 2,957.69 2,728.21 387,760.41 35,365.03
1C-3F-4H-13 kV-266.8-AWG-SA-AAC-PC (URBANA) 292,872.50 80,588.28 2,957.69 2,993.39 379,411.87 35,365.03
1C-3F-4H-13 kV-266.8-AWG-SA-ACSR-PC (URBANA) 357,158.18 80,588.28 2,957.69 2,993.39 443,697.54 35,365.03
1C-3F-3H 13 KV 336 AWG SA-AAC-PC URBANA 359,390.44 73,729.65 2,957.69 2,728.21 438,806.00 35,365.03
1C-3F-4H-13 kV-336.4-AWG-SA-AAC-PC (URBANA) 321,511.81 80,588.28 2,957.69 2,993.39 408,051.17 35,365.03
1C-3F-4H-13 kV-336.4-AWG-SA-ACSR-PC (URBANA) 381,071.79 80,588.28 2,957.69 2,993.39 467,611.15 35,365.03
1C-3F-3H 23 KV 1/0 AWG SA-AAC-PC URBANA 287,277.34 73,729.65 2,957.69 2,728.21 366,692.89 35,365.03
1C-3F-3H 23 KV 3/0 AWG SA-AAC-PC URBANA 292,165.98 73,729.65 2,957.69 2,728.21 371,581.53 35,365.03
1C-3F-4H-23 kV-3/0-AWG-SA-AAC-PC (URBANA) 310,914.14 80,588.28 2,957.69 2,993.39 397,453.50 35,365.03
1C-3F-4H-23 kV-3/0-AWG-SA-ACSR-PC (URBANA) 327,209.62 80,588.28 2,957.69 2,993.39 413,748.98 35,365.03
1C-3F-3H 23 KV 266 AWG SA-AAC-PC URBANA 329,645.58 73,729.65 2,957.69 2,728.21 409,061.14 35,365.03
1C-3F-4H-23 kV-266.8-AWG-SA-AAC-PC (URBANA) 348,393.74 80,588.28 2,957.69 2,993.39 434,933.10 35,365.03
1C-3F-4H-23 kV-266.8-AWG-SA-ACSR-PC (URBANA) 381,392.08 80,588.28 2,957.69 2,993.39 467,931.44 35,365.03
1C-3F-3H 23 KV 336 AWG SA-AAC-PC URBANA 377,432.08 73,729.65 2,957.69 2,728.21 456,847.63 35,365.03
1C-3F-4H-23 kV-336.4-AWG-SA-AAC-PC (URBANA) 396,180.22 80,588.28 2,957.69 2,993.39 482,719.59 35,365.03
1C-3F-4H-23 kV-336.4-AWG-SA-ACSR-PC (URBANA) 396,180.22 80,588.28 2,957.69 2,993.39 482,719.59 35,365.03
1C-3F-3H 33 KV 1/0 AWG SA-AAC-PC URBANA 325,400.44 73,729.65 2,957.69 2,728.21 404,815.99 35,365.03
1C-3F-4H-33 kV-3/0-AWG-SA-AAC-PC (URBANA) 336,964.45 80,588.28 2,846.36 2,993.39 423,392.47 35,365.03
1C-3F-4H-33 kV-3/0-AWG-SA-ACSR-PC (URBANA) 332,768.36 80,588.28 2,846.36 2,993.39 419,196.39 35,365.03
1C-3F-3H 33 KV 3/0 AWG SA-AAC-PC URBANA 319,819.24 73,729.65 2,957.69 2,728.21 399,234.80 35,365.03
1C-3F-4H-33 kV-266.8-AWG-SA-AAC-PC (URBANA) 350,408.22 80,588.28 2,846.36 2,993.39 436,836.25 35,365.03
1C-3F-4H-33 kV-266.8-AWG-SA-ACSR-PC (URBANA) 392,002.43 80,588.28 2,846.36 2,993.39 478,430.46 35,365.03
1C-3F-3H 33 KV 266 AWG SA-AAC-PC URBANA 333,263.01 73,729.65 2,957.69 2,728.21 412,678.56 35,365.03
1C-3F-4H-33 kV-336.4-AWG-SA-ACSR-PC (URBANA) 420,763.95 80,588.28 2,846.36 2,993.39 507,191.98 35,365.03
1C-3F-4H-33 kV-366.4-AWG-SA-AAC-PC (URBANA) 400,190.90 80,588.28 2,846.36 2,993.39 486,618.93 35,365.03
1C-3F-3H 33 KV 336 AWG SA-AAC-PC URBANA 383,045.70 73,729.65 2,957.69 2,728.21 462,461.26 35,365.03

icoNotasNota:
Estos costos no incluyen IVA
Costos por conexión de línea : $ 1,783.10